3VT2 Molded Case Circuit Breakers up to 250 A
Overcurrent releases
3/15
Siemens LV 36 · 2008
3
■
Overview
The electronic overcurrent release consists of a separate and
interchangeable unit, which is supplied with the 3VT2 switching
unit. By exchanging the overcurrent release, the range of the
rated current of the circuit breaker can be easily changed.
Overcurrent releases for 3VT2 switching units are produced with
current values of
I
n
= 100, 160 and 250 A
. The ETU LP are pro-
duced with rated currents of 160, 200 and 250 A. The releases
(including regulation of -60%) cover a current range
from 40 to
250 A
.
Tripping characteristics
Depending upon the needs for adjusting the tripping character-
istic to the protected device and to the variability of the charac-
teristic with regard to selectivity, the following releases are avail-
able:
ETU LP
They have one type of characteristic and fixed-set
I
r
and
I
i
settings.
ETU DP
They have one type of characteristic with adjustable
I
r
and
I
i
.
ETU MP
They have more kinds of characteristics with adjustable
I
r
, t
r
and
I
i
.
ETU MPS
They have more kinds of characteristics with adjustable
I
r
, t
r
,
I
i
and t
v
.
ETU LP, DP, MPand MPs overcurrent releases are intended for
3-pole 3VT2 725-.AA36-0AA0 switching units and 4-pole 3VT2
725-.AA46-0AA0 switching units with disconnecting of the N
pole.
ETU DPN
They are intended for 4-pole 3VT2 725-AA56-0AA0 switching
units with protected N pole. They have more characteristics with
adjustable
I
r
, t
r
,
I
i
and
I
N
.
NSO0_00502
t
I
L
I
NSO0_00506
t
I
L
I
I
r
I
i
t
r
NSO0_00215
t
I
L
I
I
r
50 ms
0 ms
I
i
NSO0_00214
t
I
L
S
I
I
r
I
sd
t
sd
t
r
NSO0_00531
t
I
L
I
I
r
t
r
I
i
I
N