3VT2 Molded Case Circuit Breakers up to 250 A

Overcurrent releases

3/19

Siemens LV 36 · 2008

3

Overcurrent releases ETU MP - Motors

• Direct protection for motors and generators

• Possibility for protecting lines and transformers

The 3VT9 2..-6AP00 release is intended only for 3VT2725-.AA36-

0AA0 or 3VT2725-.AA46-0AA0 switching units. The operation of

the release is controlled by a microprocessor. The release is

equipped with a thermal memory that can be disabled by turn-

ing a switch on the front panel from position T

(t)

to position T

(0)

.

After disabling of the thermal memory, the thermal release re-

mains active.

When one or two phases fail (due to current greater than

I

r

in the

remaining phases), in the M-characteristic mode, the switch will

open with a 4 s delay (so called undercurrent release).

Another parameter for adjusting the release consists of the rated

current and short-circuit tripping level. The time delay of the

short-circuit release can be set to 0 or 50 ms. The operational

state 70% of

I

r

is signalled by an LED indicator that flashes green

in a 1.5 s interval. As the load grows, the blinking frequency of

the diode increases. In case of a load larger than 110% of

I

r

, this

LED will turn red and will begin to blink red just before tripping.

On the lower part of the release cover are two photocells for

communicating with the prospective signaling unit.

The releases have tripping characteristics especially designed

for practical purposes that provide for optimal exploitation of

transformers up to 1.5

I

r

. A total of 8 characteristics can be set

on the release. Mode “M” provides 4 characteristics suitable for

protecting motors and in mode “TV” are 4 characteristics for pro-

tecting transformers and lines. The shape of each characteristic

can be changed using a selector switch.

Adjustable specifications

Order No.

Rated

cur-

rent

I

n

Over-

load

protec-

tion

I

r

t

r

(7,2 x

I

r

) Restart Instantaneous

short circuit

protection

I

i

A A s

kA

ms

40 1 (TV 1)

T

(0)

0,125

43 3 (TV 3)

T

(0

0,25

46 10 (TV 10) T

(0

0,4

48 20 (TV 20) T

(0)

0,6

0

50 20 (M 20) T

(0

0,8

55 15 (M 15) T

(0)

1,0

58 8 (M 8)

T

(0

1,25

3VT9 210-6AP00 100 61 3 (M 3)

T

(0

1,5

63 3 (M 3)

T

(t)

1,5

69 8 (M 8)

T

(t)

1,25

72 15 (M 15) T

(t)

1,0

76 20 (M 20) T

(t)

0,8

50

80 20 (TV 20) T

(t)

0,6

87 10 (TV 10) T

(t)

0,4

91 3 (TV 3)

T

(t)

0,25

100 1 (TV 1)

T

(t)

0,125

63 1 (TV 1)

T

(0)

0,2

69 3 (TV 3)

T

(0

0,4

72 10 (TV 10) T

(0

0,6

80 20 (TV 20) T

(0)

1,0

87 20 (M 20) T

(0

1,3

0

91 15 (M 15) T

(0)

1,6

100 8 (M 8)

T

(0

2,0

3VT9 216-6AP00 160 110 3 (M 3)

T

(0)

2,4

115 3 (M 3)

T

(t)

2,0

120 8 (M 8)

T

(t)

2,0

125 15 (M 15) T

(t)

1,6

130 20 (M 20) T

(t)

1,3

137 20 (TV 20) T

(t)

1,0

50

144 10 (TV 10) T

(t)

0,6

150 3 (TV 3)

T

(t)

0,4

160 1 (TV 1)

T

(t)

0,2

100 1 (TV 1)

T

(0)

0,35

110 3 (TV 3)

T

(0

0,5

115 10 (TV 10) T

(0

0,75

125 20 (TV 20) T

(0)

1,0

0

137 20 (M 20) T

(0

1,25

144 15 (M 15) T

(0)

1,5

160 8 (M 8)

T

(0

2,0

3VT9 225-6AP00 250 172 3 (M 3)

T

(0)

2,5

180 3 (M 3)

T

(t)

2,0

190 8 (M 8)

T

(t)

2,0

200 15 (M 15) T

(t)

1,5

210 20 (M 20) T

(t)

1,25

220 20 (TV 20) T

(t)

1,0

50

231 10 (TV 10) T

(t)

0,75

243 3 (TV 3)

T

(t)

0,5

250 1 (TV 1)

T

(t)

0,35