3VT2 Molded Case Circuit Breakers up to 250 A

Overcurrent releases

3/21

Siemens LV 36 · 2008

3

Overcurrent releases ETU MPS - Motors with setting timing

selectivity

• Direct protection for motors and generators

• Possibility for protecting lines and transformers

• Enables adjusting time delay of independent release

The 3VT9 2..-6AS00 release is intended for 3VT2725-.AA36-

0AA0 or 3VT2725-.AA46-0AA0 switching units. The operation of

the release is controlled by a microprocessor. The release is

equipped with a thermal memory that can be disabled by turn-

ing a switch on the front panel from position T

(t)

to position T

(0)

.

After disabling of the thermal memory, the thermal release re-

mains active.

When one or two phases fail (due to current greater than

I

r

in the

remaining phases), in the M-characteristic mode, the switch will

open with a 4 s delay (so called undercurrent release).

Another parameter for adjusting the release is the rated current

and tripping level of the delayed short-circuit release. The time

delay (t

sd

) can be set on the delayed short-circuit release at 0,

100, 200 or 300 ms. The operational state 70% of

I

r

is signalled

by an LED indicator that flashes green in a 1.5 s interval. As the

load grows, the blinking frequency of the diode increases. In

case of a load larger than 110% of

I

r

, this LED will turn red and

will begin to blink red just before tripping. On the lower part of

the release cover are two photocells for communicating with the

prospective signaling unit.

The releases have tripping characteristics especially designed

for practical purposes that provide for optimal exploitation of

transformers up to 1.5

I

r

. A total of 8 characteristics can be set

on the release. Mode “M” provides 4 characteristics suitable for

protecting motors, and in mode “TV” are 4 characteristics for

protecting transformers and lines. The shape of each character-

istic can be changed using a selector switch.

Adjustable specifications

Order No.

Rated

cur-

rent

I

n

Over-

load

protec-

tion

I

r

t

sd

(7.2 x

I

r

) Restart Short circuit

protection

(short time

delayed)

I

i

A A S

kA

ms

40 1 (TV 1)

T

(0)

3

43 3 (TV 3)

T

(0)

5

0

46 10 (TV 10) T

(0)

7

48 20 (TV 20) T

(0)

9

50 20 (M 20) T

(0)

3

55 15 (M 15) T

(0)

5

100

58 8 (M 8)

T

(0)

7

3VT9210-6AS00 100 61 3 (M 3)

T

(0)

9

63 3 (M 3)

T

(t)

3

69 8 (M 8)

T

(t)

5

200

72 15 (M 15) T

(t)

7

76 20 (M 20) T

(t)

9

80 20 (TV 20) T

(t)

3

87 10 (TV 10) T

(t)

5

300

91 3 (TV 3)

T

(t)

7

100 1 (TV 1)

T

(t)

9

63 1 (TV 1)

T

(0)

3

69 3 (TV 3)

T

(0)

5

0

72 10 (TV 10) T

(0)

7

80 20 (TV 20) T

(0)

9

87 20 (M 20) T

(0)

3

91 15 (M 15) T

(0)

5

100

100 8 (M 8)

T

(0)

7

3VT9216-6AS00 160 110 3 (M 3)

T

(0)

9

115 3 (M 3)

T

(t)

3

120 8 (M 8)

T

(t)

5

200

125 15 (M 15) T

(t)

7

130 20 (M 20) T

(t)

9

137 20 (TV 20) T

(t)

3

144 10 (TV 10) T

(t)

5

300

150 3 (TV 3)

T

(t)

7

160 1 (TV 1)

T

(t)

9

100 1 (TV 1)

T

(0)

3

110 3 (TV 3)

T

(0)

5

0

115 10 (TV 10) T

(0

7

125 20 (TV 20) T

(0))

9

137 20 (M 20) T

(0)

3

144 15 (M 15) T

(0)

5

100

160 8 (M 8)

T

(0)

7

3VT9225-6AS00 250 172 3 (M 3)

T

(0)

9

180 3 (M 3)

T

(t)

3

190 8 (M 8)

T

(t)

5

200

200 15 (M 15) T

(t)

7

210 20 (M 20) T

(t)

9

220 20 (TV 20) T

(t)

3

231 10 (TV 10) T

(t)

5

300

243 3 (TV 3)

T

(t)

7

250 1 (TV 1)

T

(t)

9