3VT2 Molded Case Circuit Breakers up to 250 A

Circuit breakers · Switch disconnectors

3/12

Siemens LV 36 · 2008

3

Technical specifications

available

-- unavailable

+ in preparation

Specifications

Circuit breakers

Switch disconnectors

Standards

EN 60947-2, IEC 60947-2

EN 60947-3, IEC 60947-3

Approval marks

Number of poles

3, 4

Rated current

I

n

A

100, 160, 200, 250

--

Rated uninterrupted current

I

u

A

250

Rated operational current

I

e

A

--

250

Rated operational voltage U

e

V

AC max. 690

AC max. 690

DC max. 440

Rated frequency f

n

Hz

50/60

Rated impulse withstand voltage U

imp

kV 8

Rated insulation voltage U

i

V

690

Utilization category (selectivity) AC 690 V

A

--

Utilization category (switching mode)

AC 690 V

--

AC-23 B

DC 440 V

--

DC-23 B

Rated short-time withstand current U

e

= AC 690 V

I

cw

/t

2,5 kA/1 s

3 kA/5 s

Series U

e

3VT2 N

3VT2 H U

e

--

Rated ultimate short-circuit breaking capacity (rms value)

1)

I

cu

60 kA

36 kA

16 kA

10 kA

100 kA

65 kA

25 kA

13 kA

AC 230 V

AC 415 V

AC 500 V

AC 690 V

--

Rated short-circuit service breaking capacity (rms value)

I

cs

/U

e

30 kA

18kA

8kA

5kA

50 kA

36 kA

13 kA

8 kA

AC 230 V

AC 415 V

AC 500 V

AC 690 V

--

Rated short-circuit making capacity (peak value)

I

cm

/U

e

75 kA

140 kA

AC 415 V 4 kA/AC 15 V

4 kA/AC440 V

Off-time at

I

cu

ms

10

--

Losses per pole at

I

n

= 250 A

W 18

Mechanical endurance

cycles 30 000

Electrical endurance (U

e

= AC 415 V )

cycles 3 000

Switching frequency

cycles

/hr

120

Operating force

N 80

Front-side device protection

IP40

Terminal protection

IP20

Operating conditions

Reference ambient temperature

°C 40

Ambient temperature range

°C -40 ... +55

Working environment

dry and tropical climate

Pollution degree

3

Max. elevation

m 2000

Seismic resistance

Hz

3g (8 ... 50)

Design modifications

Front/rear connection

/

Plug-in design

/+

Withdrawable design

/+

Accessories

Switches – auxiliary/relative/signal/leading

/

/

/

Shunt release/with signal switch

Undervoltage release/with leading switch/with signal switch

/

Front manual operating mechanism/lateral operating mechanism

at the right/left hand side

/

Mechanical interlocking of manual operating mechanisms,

by Bowden wire

/

Motorized operating mechanism/with operations counter

/

Locking-type knob

Bolt sealing inset/additional cover for overcurrent release

/