3VT2 Molded Case Circuit Breakers up to 250 A

Circuit breakers · Switch disconnectors

3/11

Siemens LV 36 · 2008

3

Design

Installation and connection

Main circuit

• Is connected, using Cu or Al busbars or cables, and possibly

cables with cable lugs

• For further connecting options, connecting sets are produced

(see page 3/9).

• Generally, conductors from the power supply are connected

to input terminals 1, 3, 5 and conductors from the load to ter-

minals 2, 4, 6. But it is possible to exchange this connection

(exchanging input and output terminals without limiting rated

short-circuit ultimate breaking capacity

I

cu

)

• In case of feed-in from below, the circuit breakers/switch dis-

connectors must be fitted with 3VT9 300-8CE30 phase barri-

ers also on the side of terminals 2, 4, 6

• We recommend painting the connecting busbars with different

colors

• Input and output connectors/busbars must be mechanically

reinforced in order to avoid transferring electrodynamic forces

to the circuit breaker during short circuiting

• The way of connecting the power circuit must observe the

deionization space of the circuit breaker/switch disconnector

(see page 3/42)

.

Auxiliary circuits

• Switches, shunt releases or undervoltage releases are con-

nected using flexible 0.5 ... 1 mm

2

Cu conductors to terminals

on these devices

• Motorized operating mechanism and auxiliary circuits of the

plug-in or withdrawable design are connected using a con-

nector.

Recommended cross-sections of cables, busbars and flexibars

for fixed-mounted, plug-in and withdrawable designs

Maximum circuit breaker/switch disconnector loads

in accordance with the ambient temperature

3VT2 circuit breaker/switch disconnector connection to pole

by 1 x 120 mm

2

Cu cable

Conductor cross-sections of main terminals

Rated current

I

n

Permissible cross-section

S

Busbars

W x H

Cu

Al

Cu

Al

A

mm

2

mm

2

mm

mm

40

10

16

50

10

16

63

16

25

80

25

35

100

35

50

20 x 2

25 x 2

125

50

70

25 x 2

25 x 3

160

70

95

25 x 3

25 x 4

200

95

120

25 x 4

25 x 5

250

120

150

25 x 5

25 x 6

50 °C

55 °C

60 °C

65 °C

70 °C

250 A

250 A

250 A

250 A

250 A

Order No.

Rated

current

I

n

Maximum permissible conductor cross-section

Cable type

Sector-shaped

conductor,

stranded

Sector-shaped

conductor, solid

Round

conductor, stranded

Round

conductor,

solid

Busbars and

cable lugs

Technical

information

W x H

A

mm

2

mm

2

mm

2

mm

2

mm

Page

3VT9 200-4TA30

250

25 x ...

3VT9 200-4RC30

250

25 x ...

3/45, 3/55

3VT9 215-4TF00

3VT9 200-4TC30

250

16 ... 150 Cu

10 ...150 Cu

16 ... 150

10 ...150 Cu

3VT9 200-4TC00

3VT9 215-4TD30

250

25 ... 150 Cu/Al

16 ...150 Cu/Al

25 ... 150 Cu/Al

16 ... 150 Cu/Al

3VT9 215-4TD00

3VT9 224-4TD30

250

150 ... 240 Cu/Al

120 ... 240 Cu/Al

150 ... 240 Cu/Al

120 ... 240 Cu/Al

3/44, 3/55

3VT9 224-4TD00

3VT9 215-4TF30

250

2 x (25 ... 150) Cu/Al

2 x (16 ... 150) Cu/Al

2 x (25 ... 150) Cu/Al

2 x (16 ... 150) Cu/Al

3/44, 3/55

3VT9 215-4TF00

3VT9 224-4TF30

250

2 x (150 ... 240) Cu/Al 2 x (120 ... 240) Cu/Al 2 x (150 ... 240) Cu/Al 2 x (120 ... 240) Cu/Al

3/44, 3/56

3VT9 224-4TF00

3VT9 203-4TF30

250

6 x (6 ... 35) Cu/Al

6 x (6 ... 35) Cu/Al

6 x (6 ... 35) Cu/Al

6 x (6 ... 35) Cu/Al

3/45, 3/56

3VT9 203-4TF00

3VT9 200-4ED30

250

3/46

3VT9 200-4EE30

250

3/46

3VT9 200-4TN30

10/16

1,5 ... 2,54 ... 6 Cu flexible conductor