Table of Contents Table of Contents
Previous Page  210 / 221 Next Page
Information
Show Menu
Previous Page 210 / 221 Next Page
Page Background

203

IEC 60228 : 2004 - 11 CONDUCTOR TABLES

MINIMUM AND MAXIMUM DIAMETERS OF STRANDED COMPACTED CIRCULAR COPPER, ALUMINIUM AND ALUMINIUM ALLOY CONDUCTORS

Cross-sectional area

[mm

2

]

Stranded compacted circular conductors (Class 2)

Minimum diameter

[mm]

Maximum diameter

[mm]

10

3,6

4,0

16

4,6

5,2

25

5,6

6,5

35

6,6

7,5

50

7,7

8,6

70

9,3

10,2

95

11,0

12,0

120

12,3

13,5

150

13,7

15,0

185

15,3

16,8

240

17,6

19,2

300

19,7

21,6

400

22,3

24,6

500

25,3

27,6

630

28,7

32,5

NOTES: - The dimensional limits of Aluminium conductors with cross-sectional areas above 630 mm

2

are not given as the compaction technology is not generally estabilished.

- The values are given for compacted Copper conductors in the size range 1,5 mm

2

to 6 mm

2

.

MAXIMUM DIAMETERS OF CIRCULAR COPPER CONDUCTORS: SOLID, NON COMPACTED STRANDED AND FLEXIBLE

Cross sectional area

[mm

2

]

Conductors in cables for fixed installations

Flexible conductors (Classes 5 and 6)

Maximum diameter [mm]

Solid (Class 1)

Maximum diameter [mm]

Stranded (Class 2)

Maximum diameter [mm]

0,5

0,9

1,1

1,1

0,75

1,0

1,2

1,3

1

1,2

1,4

1,5

1,5

1,5

1,7

1,8

2,5

1,9

2,2

2,4

4

2,4

2,7

3,0

6

2,9

3,3

3,9

10

3,7

4,2

5,1

16

4,6

5,3

6,3

25

a

5,7

6,6

7,8

35

a

6,7

7,9

9,2

50

a

7,8

9,1

11,0

70

a

9,4

11,0

13,1

95

a

11,0

12,9

15,1

120

a

12,4

14,5

17,0

150

a

13,8

16,2

19,0

185

15,4

18,0

21,0

240

17,6

20,6

24,0

300

19,8

23,1

27,0

400

22,2

26,1

31,0

500

-

29,2

35,0

630

-

33,2

39,0

800

-

37,6

-

1000

-

42,2

-

NOTE The values given for flexible conductors represent both class 5 and class 6 conductors.

a

Solid Copper conductor shaving cross-sectional areas of 25 mm

2

and above are for particular types of cable, e.g. mineral insulated, and not for general purposes.

MINIMUM AND MAXIMUM DIAMETERS OF CIRCULAR ALUMINIUM CONDUCTORS

Cross-sectional area

[mm

2

]

Solid conductors (Class 1)

Minimum diameter

[mm]

Maximum diameter

[mm]

10

3,4

3,7

16

4,1

4,6

25

5,2

5,7

35

6,1

6,7

50

7,2

7,8

70

8,7

9,4

95

10,3

11,0

120

11,6

12,4

150

12,9

13,8

185

14,5

15,4

240

16,7

17,6

300

18,8

19,8

400

21,2

22,2

500

24,0

25,1

630

27,3

28,4

800

30,9

32,1

1000

34,8

36,0

1200

37,8

39,0