13/10

Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

13

Combined Category C, B tested protector (to BS EN 61643) suitable to protect

PCs and other computer equipment on systems using 9, 15 or 25 pins. For use

on lines running within buildings at boundaries up to LPZ 2 through to LPZ 3

to protect sensitive electronic equipment.

Telecoms & computer line protection

ESP LA & LB Series

TECHNICAL NOTE:

ESP LA... and ESP LB... protectors are designed only for use on cables

running within a building (typically LPZ 2) to offer local protection to equipment. They therefore

will not be able to handle the higher level transients that occur when lines between buildings

are protected. ESP LA... and ESP LB... protectors should not be used in such an application

(up to LPZ

0

) where high energy ESP lightning barriers (such as ESP E Series) should be

employed. If they are used in lines between buildings, there is a high risk of the protector

being overloaded and destroyed during transient activity. Connected equipment will, in most

cases, still be protected, but there is a small risk that equipment will suffer damage in

such circumstances.

Installation

Simple plug-in connection to the communication port,

between the equipment to be protected and its incoming

data cable. Make suitable attachment to earth.

Full product range order codes can be found on pages 17/8-17/9

NOTE:

For cabling up to Cat-6 with RJ45 connections (running external to the building) and local protection for up to Cat-6 with RJ45 connections,

(running within a building) products are also available. For protection of legacy coaxial Ethernet networks, please contact us for details of our ESP ThinNet

and ESP ThickNet protectors.

Features & benefits

–– Let-through voltage below equipment susceptibility levels

–– Negligible in-line resistance

–– Suitable for equipment using “D” connectors - DB-9,

DB-15 and DB-25

–– ESP LA-5/25 protects pins 1, 2, 3, 7 & 20 to earth/shell.

Note pin 1 is connected to earth

–– ESP LA-25/25 and ESP LB-25/25 protects all pins. Note

pin 1 is connected to earth/shell

–– ESP LA-9/9, ESP LB-9/9, ESP LA-15/15 and ESP

LB-15/15 protect all pins

–– Sturdy plastic housing

–– Male/female connectors allow easy plug-in installation

without rewiring

–– Earthed via shell and supplementary earth strap

Application

Use on cables running within a building to protect equipment

locally from transients induced on to data cables from the

magnetic field caused by a lightning strike.

–– For Asynchronous RS 232 systems, use ESP LA-5/25

–– For RS 232 systems, use ESP LA-25/25, ESP LA-9/9

or ESP LA-15/15

–– For RS 422, RS 423 and RS 485 systems, use ESP

LB-9/9, ESP LB-15/15 or ESP LB-25/25