Table of Contents Table of Contents
Previous Page  265 / 336 Next Page
Information
Show Menu
Previous Page 265 / 336 Next Page
Page Background

Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

13/7

13

ESP KT & KE Series - Technical specification

Electrical specification

ESP KT1

ESP KT1/PTC

ESP KT2

ESP K10T1

ESP K10T1/PTC

ESP K10T2

ABB order code

7TCA085400R0135 7TCA085400R0034 7TCA085400R0136 7TCA085400R0130 7TCA085400R0131 7TCA085400R0133

Maximum working

– line to line

296 V

296 V

5 V

296 V

296 V

5 V

voltage

U

c

(1)

– line to earth

296 V

296 V

58 V

296 V

296 V

58 V

Current rating (signal)

300 mA

145 mA

300 mA

300 mA

145 mA

300 mA

In-line resistance (per line ±10%)

4.4 Ω

Bandwidth (-3 dB 50 Ω system)

20 MHz

20 MHz

20 MHz

20 MHz

19 MHz

19 MHz

Transient specification

ESP KT1

ESP KT1/PTC

ESP KT2

ESP K10T1

ESP K10T1/PTC ESP K10T2

Let-through voltage (all conductors)

(2)

U

p

C2 test 4 kV 1.2/50 μs,

– line to line

395 V

395 V

28 V

395 V

395 V

28 V

2 kA 8/20 μs to

BS EN/EN/IEC 61643-21

– line to earth

395 V

395 V

88 V

395 V

395 V

88 V

C1 test 1 kV, 1.2/50 μs,

– line to line

390 V

390 V

23 V

390 V

390 V

23 V

0.5 kA 8/20 μs to

BS EN/EN/IEC 61643-21

– line to earth

390 V

390 V

63 V

390 V

390 V

63 V

B2 test 4 kV 10/700 μs to – line to line

298 V

298 V

26 V

298 V

298 V

26 V

BS EN/EN/IEC 61643-21

– line to earth

298 V

298 V

65 V

298 V

298 V

65 V

5 kV, 10/700 μs

(3)

– line to line

300 V

300 V

27 V

300 V

27 V

27 V

– line to earth

300 V

300 V

80 V

300 V

80 V

80 V

Maximum surge current

(4)

D1 test 10/350 μs to – line to line

1 kA

BS EN/EN/IEC 61643-21: – line to earth

2 kA

8/20 μs to ITU-T K.45:2003, – line to line

5 kA

IEEE C62.41.2:2002: – line to earth

10 kA

Power Faults specification

ESP KT1

ESP KT1/PTC

ESP KT2

ESP K10T1

ESP K10T1/PTC ESP K10T2

Power/Line Cross and Power Induction - tests to: ITU-T (formerly CCITT) K.20, K.21 and K.45, Telcordia GR-1089-CORE, Issue 2:2002, UL 60950/IEC 950

Power/line cross

110/230 Vac

110/230 Vac

(15 min)

(15 min)

Power induction

600 V, 1 A

600 V, 1 A

(0.2 sec)

(0.2 sec)

Mechanical specification

ESP KT1, ESP KT2, ESP KT1/PTC

ESP K10T1, ESP K10T2, ESP K10T1/PTC ESP KE10

Temperature range

-40 to +80 ºC

Connection type

To LSA-PLUS disconnection modules (BT part number 237A)

Earth connection

Via ESP KE10 earth bar

Via integral earth clip/external

M4 bush

Material

FR Polymer UL-94 V-0

Stainless Steel

Weight: – Unit

0.01 kg

0.10 kg

0.01 kg

– Packaged

0.12 kg (per 10)

0.12 kg

0.10 kg (per 10)

Dimensions

See diagram below

(1)

Maximum working voltage (DC or AC peak) at 10 μA for

ESP KT1, ESP KT1/PTC, ESP K10T1, ESP K10T1/PTC and at

5 μA for ESP KT2 and ESP K10T2

(2)

The maximum transient voltage let-through of the protector

throughout the test (±10%), line to line & line to earth,

both polarities. Response time < 10 ns

(3)

Test to IEC 61000-4-5:2006, ITU-T (formerly CCITT) K.20,

K.21 and K.45,Telcordia GR-1089-CORE, Issue 2:2002,

ANSI TIA/EIA/IS-968-A:2002 (formerly FCC Part 68)

(4)

The installation and connections external to the protector

may limit the capability of the protector

22 mm

Depth: 21 mm

110 mm

110 mm

22 mm

9.5 mm

59 mm

40 mm

20 mm

40 mm

59 mm

Telecoms & computer line protection