Total Solution to Earthing & Lightning Protection |
9AKK106354A3360
13/7
13
ESP KT & KE Series - Technical specification
Electrical specification
ESP KT1
ESP KT1/PTC
ESP KT2
ESP K10T1
ESP K10T1/PTC
ESP K10T2
ABB order code
7TCA085400R0135 7TCA085400R0034 7TCA085400R0136 7TCA085400R0130 7TCA085400R0131 7TCA085400R0133
Maximum working
– line to line
296 V
296 V
5 V
296 V
296 V
5 V
voltage
U
c
(1)
– line to earth
296 V
296 V
58 V
296 V
296 V
58 V
Current rating (signal)
300 mA
145 mA
300 mA
300 mA
145 mA
300 mA
In-line resistance (per line ±10%)
4.4 Ω
Bandwidth (-3 dB 50 Ω system)
20 MHz
20 MHz
20 MHz
20 MHz
19 MHz
19 MHz
Transient specification
ESP KT1
ESP KT1/PTC
ESP KT2
ESP K10T1
ESP K10T1/PTC ESP K10T2
Let-through voltage (all conductors)
(2)
U
p
C2 test 4 kV 1.2/50 μs,
– line to line
395 V
395 V
28 V
395 V
395 V
28 V
2 kA 8/20 μs to
BS EN/EN/IEC 61643-21
– line to earth
395 V
395 V
88 V
395 V
395 V
88 V
C1 test 1 kV, 1.2/50 μs,
– line to line
390 V
390 V
23 V
390 V
390 V
23 V
0.5 kA 8/20 μs to
BS EN/EN/IEC 61643-21
– line to earth
390 V
390 V
63 V
390 V
390 V
63 V
B2 test 4 kV 10/700 μs to – line to line
298 V
298 V
26 V
298 V
298 V
26 V
BS EN/EN/IEC 61643-21
– line to earth
298 V
298 V
65 V
298 V
298 V
65 V
5 kV, 10/700 μs
(3)
– line to line
300 V
300 V
27 V
300 V
27 V
27 V
– line to earth
300 V
300 V
80 V
300 V
80 V
80 V
Maximum surge current
(4)
D1 test 10/350 μs to – line to line
1 kA
BS EN/EN/IEC 61643-21: – line to earth
2 kA
8/20 μs to ITU-T K.45:2003, – line to line
5 kA
IEEE C62.41.2:2002: – line to earth
10 kA
Power Faults specification
ESP KT1
ESP KT1/PTC
ESP KT2
ESP K10T1
ESP K10T1/PTC ESP K10T2
Power/Line Cross and Power Induction - tests to: ITU-T (formerly CCITT) K.20, K.21 and K.45, Telcordia GR-1089-CORE, Issue 2:2002, UL 60950/IEC 950
Power/line cross
–
110/230 Vac
–
–
110/230 Vac
–
(15 min)
(15 min)
Power induction
–
600 V, 1 A
–
–
600 V, 1 A
–
(0.2 sec)
(0.2 sec)
Mechanical specification
ESP KT1, ESP KT2, ESP KT1/PTC
ESP K10T1, ESP K10T2, ESP K10T1/PTC ESP KE10
Temperature range
-40 to +80 ºC
–
Connection type
To LSA-PLUS disconnection modules (BT part number 237A)
–
Earth connection
Via ESP KE10 earth bar
Via integral earth clip/external
–
M4 bush
Material
FR Polymer UL-94 V-0
Stainless Steel
Weight: – Unit
0.01 kg
0.10 kg
0.01 kg
– Packaged
0.12 kg (per 10)
0.12 kg
0.10 kg (per 10)
Dimensions
See diagram below
(1)
Maximum working voltage (DC or AC peak) at 10 μA for
ESP KT1, ESP KT1/PTC, ESP K10T1, ESP K10T1/PTC and at
5 μA for ESP KT2 and ESP K10T2
(2)
The maximum transient voltage let-through of the protector
throughout the test (±10%), line to line & line to earth,
both polarities. Response time < 10 ns
(3)
Test to IEC 61000-4-5:2006, ITU-T (formerly CCITT) K.20,
K.21 and K.45,Telcordia GR-1089-CORE, Issue 2:2002,
ANSI TIA/EIA/IS-968-A:2002 (formerly FCC Part 68)
(4)
The installation and connections external to the protector
may limit the capability of the protector
22 mm
Depth: 21 mm
110 mm
110 mm
22 mm
9.5 mm
59 mm
40 mm
20 mm
40 mm
59 mm
Telecoms & computer line protection
ESP KT & KE Series