Total Solution to Earthing & Lightning Protection |
9AKK106354A3360
13
Combined Category D, C, B tested protector (to BS EN 61643) suitable to
protect twisted pair Ethernet networks, including Power over Ethernet (PoE),
with RJ45 connections. For use at boundaries up to LPZ
0
to protect
against flashover (typically the service entrance location) through to LPZ 3
to protect sensitive electronic equipment.
Telecoms & computer line protection
ESP Cat-5 & Cat-6 Series
Installation
Connect in series with the network cable, either:
– Near to where it enters or leaves the building, or
– As it enters the network hub, or
– Close to the equipment being protected
This should be close to the system’s earth star point
(to enable a good connection to earth).
Accessories
ESP CAT5e/UTP-1
1 metre cable with unshielded RJ45
connections
ESP CAT6/STP-2
2 metre screened cable with shielded
RJ45 connections
Full product range order codes can be found on pages 17/8-17/9
Plug-in series connection
ELECTRONICSYSTEMSPROTECTION
Plug-inLightningBarrier
WilfordRoad,
Nottingham,
NG21EB,UK
DIRTY
CLEAN
Earth
To equipment
From
line
TECHNICAL NOTE:
The
interfaces used in Ethernet
networks incorporate an isolation
transformer which gives these
systems an inbuilt immunity to
transients between line and earth
of 1,500 Volts or more.
Features & benefits
–– Suitable for systems signalling on up to eight wires of either
shielded or unshielded twisted pair cable
–– Very low let-through voltage (enhanced protection to
IEC/BS EN 62305) between all lines - Full Mode design
capable of handling partial lightning currents as well as
allowing continual operation of protected equipment
–– Repeated protection in lightning intense environments
–– Unlike some competing devices, the ethernet SPDs
provide effective protection without impairing the system’s
normal operation
–– Low capacitance circuitry prevents the start-up signal
degradation associated with other types of network protector
–– Low in-line resistance minimizes unnecessary reductions in
signal strength to maximize signalling distance
–– Sturdy ABS housing with convenient holes for flat
mounting, or vertically via TS35 ‘Top Hat’ DIN rail
–– Substantial earth connection to enable effective earthing
–– Will protect all PoE powering modes A and B.
Application
Use these protectors on network cables that travel between
buildings to prevent damage to equipment, e.g. computers,
servers, repeaters and hubs. Suitable for computer networks
up to Cat-6A cabling.
–– To protect up to 100baseT networks with Cat-5/Cat-5e
cabling use ESP Cat-5e
–– To protect up to 1000baseT/ 10GbaseT networks with
Cat-6/Cat-6A cabling use ESP Cat-6
–– To protect up to 100baseT Power over Ethernet (PoE)
networks with Cat-5/Cat-5e use ESP Cat-5e/PoE
–– To protect up to 1000baseT/ 10GbaseT Power over
Ethernet (PoE) networks with Cat-6/Cat-6A cabling use
ESP Cat-6/PoE
For further application information, see separate Application
Note AN004 (contact us for a copy).
NOTE:
To protect datacomms systems based on twisted pairs, use the ESP D, E or H Series. Local protection for networked equipment is also available.
For protection of legacy coaxial Ethernet networks, please contact us for details of our ESP ThinNet and ESP ThickNet protectors.
PoE+
Compliant
IEEE 802.3at
PoE
Modes
A & B