Total Solution to Earthing & Lightning Protection |
9AKK106354A3360
13
Combined Category D, C, B tested protector (to BS EN 61643) suitable for use
on ten line LSA-PLUS disconnection modules to PBX telephone exchanges, ISDN
and other telecoms equipment with LSA-PLUS disconnection modules. For use
at boundaries up to LPZ
0
to protect against flashover (typically the service
entrance location) through to LPZ 3 to protect sensitive electronic equipment.
Telecoms & computer line protection
ESP KT & KE Series
NOTE:
For individual telephone lines and lines at unmanned sites the high performance ESP TN, ready-boxed derivative ESP TN/BX or ESP TN/2BX,
or plug-in ESP TN/JP or ESP TN/RJ11 Series should be used. For plug-in S/T interface ISDN protection, use the ESP TN or ISDN Series protectors.
Installation
Install protectors on all lines that enter or leave each building
(including extensions to other buildings). Identify the lines
requiring protection and plug-in the protector (ensuring the
correct orientation) for a series connection. Plug ESP K10T1/2
directly into each disconnection module requiring protection.
ESP KT1/2 and ESP KT1/PTC must be installed via the ESP
KE10 earth bar. Clip an ESP KE10 on to the disconnection
module and plug an ESP KT1/2 or ESP KT1/PTC in to
each line on the module that needs protecting. In the unlikely
situation that the protector is damaged, it will sacrifice
itself and fail short circuit, taking the line out of commission,
indicating it needs replacing and preventing subsequent
transients from damaging equipment.
For further information on global telephony applications, see
separate Application Note AN005 (contact us for a copy).
Features & benefits
–– Low cost protection for large numbers of data and signal lines
–– Very low let-through voltage (enhanced protection to
IEC/BS EN 62305) between all lines - Full Mode protection
–– Full Mode design capable of handling partial lightning
currents as well as allowing continual operation of
protected equipment
–– Repeated protection in lightning intense environments
–– Colour of housing distinguishes electrically different
protectors - avoids confusion when installed together
on the same distribution frame
–– Quick and easy plug-in installation, with ‘bump’
location feedback
–– Under power line cross conditions /PTC versions offer safe
disconnection during fault duration. Unit auto-resets once
fault corrected
–– At larger installations ESP K10T1/2 and ESP K10T1/PTC
provide all in one protection for all ten lines on LSA-PLUS
disconnection modules
–– Use the ESP KE10 to provide trouble free earthing for
up to ten ESP KT1/2 and ESP KT1/PTC (per
disconnection module)
–– ESP K10T1/2 and ESP K10T1/PTC have an integral earth
connection, and an external M4 earth bush for use with
non-metallic LSA-Plus frames
–– ESP KT1/PTC and ESP K10T1/PTC have resettable
overcurrent protection and are rated for power cross faults
–– ESP KT1, ESP KT1/PTC, ESP K10T1 and ESP K10T1/PTC
are suitable for telecoms applications in accordance with
Telcordia and ANSI Standards
Application
–– For PSTN (e.g POTS, dial-up, lease line, T1/E1, *DSL
and Broadband) and U interface ISDN lines, use ESP KT1
(or ESP KT1/PTC) and ESP K10T1 (or ESP K10T1/PTC)
–– For S/T interface ISDN lines, use ESP KT2 and ESP K10T2
–– Protect single lines with ESP KT1, ESP KT2 or
ESP KT1/PTC
–– Protect all ten lines on a disconnection module with
ESP K10T1/2
Full product range order codes can be found on pages 17/8-17/9