At distribution boards, the

protector can be installed either

on the load side of the incoming

isolator, or on the closest outgoing

way to the incoming supply.

Connect, with very short

connecting leads, to phase,

neutral and earth.

For TT installations, contact Furse.

Furse, Wilford Road, Nottingham, NG2 1EB • Tel: +44 (0)115 964 3700 • Email:

enquiry@furse.com

• Web:

www.furse.com

ESP D1 Series (Single Phase)

TSC-0912 - 09.10.12

Very low let-through voltage (enhanced protection to BS EN 62305)

between all sets of conductors (phase to neutral, phase to earth, neutral

to earth - Full Mode protection)

Full mode design capable of handling partial lightning currents as well

as allowing continual operation of protected equipment

Repeated protection in lightning intense environments

Innovative multiple thermal disconnect technology for safe

disconnection from faulty or abnormal supplies (without compromising

protective performance)

Three way visual indication of protection status and advanced

pre-failure warning so you need never be unprotected

Remote indication facility allows pre-failure warning to be linked to a

building management system, buzzer or light

Changeover active volt-free contact enables the protector to be used to

warn of phase loss (i.e. power failure, blown fuses etc)

Flashing warning of potentially fatal neutral to earth supply faults (due

to incorrect earthing, wiring errors or unbalanced conditions)

Through terminal facility allows series connection on low current

supplies to eliminate high additive voltage associated with connecting

leads on units installed in parallel

Compact space saving DIN housing

Features and benefits

Combined Type 1, 2 and 3 tested protector (to BS EN 61643) for use

on single phase mains power distribution systems primarily to

protect connected electronic equipment from transient overvoltages

on the mains supply, e.g. computer, communications or control

equipment. For use at boundaries up to LPZ

0

B

to protect against

flashover (typically the main distribution board location, with

multiple metallic services entering) through to LPZ 3 to protect

sensitive electronic equipment.

Install in parallel, within the power

distribution board or directly (via

fuses) on to the supply feeding

equipment. Can be installed in

series for low current supplies - see

installation instructions.

Installation

Weatherproof enclosure

WBX D4

Accessories

Parallel connection of ESP 120 D1,

ESP 240 D1 and ESP 277 D1 series to single

phase supplies (fuses not shown for clarity)

L

N

T2

C

T1

I

imp

4kA

I

n

20kA

I

max

oc

40kA

U

6kV

c

z

ac

U

280V 47-63H

B

D

T3

125AgL

!

GREEN

FULLPROTECTION

GREEN&RED REDUCED

PROTECTION

(replaceunit)

RED NOPROTECTION

WARNING:Iflit/

flashingdisconnect

unit&checkNeutral

toEarth voltage

EN/IEC 61643

PATENT

APPLIED

FOR

STATUS INDICATION

ESP 240D1

L

L

1

N

1

N

11

14

12

STATUS

L

1

N

Series connection of ESP 120 D1, ESP 240 D1

and ESP 277 D1 to single phase supplies up

to 125 A (fuses not shown for clarity)

L

1

N

L

N

T2

C

T1

I

imp

4kA

I

n

20kA

I

max

oc

40kA

U

6kV

c

z

ac

U

280V 47-63H

B

D

T3

125AgL

!

GREEN

FULLPROTECTION

GREEN&RED REDUCED

PROTECTION

(replaceunit)

RED NOPROTECTION

WARNING: If lit /

flashingdisconnect

unit&checkNeutral

toEarthvoltage

EN/IEC 61643

PATENT

APPLIED

FOR

STATUS INDICATION

ESP 240D1

L

L

1

N

1

N

11

14

12

STATUS

If you desire a protector with an extra high maximum surge current use the ESP M2 or

ESP M4 series. If your supply is fused at 16 Amps, or less, the in-line protectors (and their

ready-boxed derivatives) may be more suitable.