36
www.emergi-lite.co.ukEMEX 110
EMEX 110
Order codes
3 hour 110V AC/DC systems
Rating
KVA
Watts
Cabinet quantity Part No.
2.0
1,000
1
ELD9100.130
2.0
1,600
1
ELD9100.131
2.0
2,000
1
ELD9100.132
3.0
2,700
1
ELD9100.133
4.0
3,600
1
ELD9100.134
5.5
4,860
2
ELD9100.135
5.5
5,400
2
ELD9100.136
1 hour 110V AC/DC systems
Rating
KVA
Watts
Cabinet quantity Part No.
2.0
1,900
1
ELD9100.120
3.0
2,700
1
ELD9100.121
4.0
4,000
1
ELD9100.122
5.5
5,500
1
ELD9100.123
60Hz Central power supply systems available. Please
contact Emergi-Lite for details.
Other system sizes and ratings are available – please
contact us if your requirements are not shown here.
Remote alarm
British Standard BS 5266 Part 8 (BS EN 50172)
section 7.2.2 requires that a visual daily check of
the central power supply alarms is made. It is also
a requirement that the CPS should be located in a
secure area, which is typically a locked switch room in
the basement.
We offer an optional Remote Alarm Unit (RAU),
assists the user to identify any alarm conditions.
Remote Alarm Unit
RAU/240V
ELD0075.003A
Remote alarm unit providing both audible and visual
fault indication with mute facility. The RAU requires a
local 220 – 240VAC supply and should be linked to the
static inverter unit by a two core cable.
Cabinet size
Overall depth of 725mm is required to allow a
ventilation gap of 75mm (rubber back-stop provided
ensures this distance is maintained).
Cabinets may be mounted side-by-side since no side
ventilation is required.
Standard cabinet size is 750mm wide x 650mm deep x 1800mm tall. For larger installations, cabinets are mounted
side by side to provide sufficient accommodation for the batteries.