Background Image
Table of Contents Table of Contents
Previous Page  38 / 52 Next Page
Information
Show Menu
Previous Page 38 / 52 Next Page
Page Background

38

www.emergi-lite.co.uk

Conversion modules

EMEL

A conversion module is required for a conventional fluorescent

mains luminaire when it is powered from a Central Power Supply

System for emergency lighting use. This provides fail-safe

emergency operation from the CPS supply upon failure of the

local lighting circuit whilst retaining the switchable function of the

luminaire under mains healthy conditions.

The MDG inverter module has been designed to efficiently operate

4 – 100 watt 4-pin fluorescent lamps, from 50 volt or 110 volt AC/DC

Central Power Supply Systems.

Features and benefits

l

Ideally suited for individual local circuit failure monitoring via the

connection of an unswitched supply

l

Incorporates an integral five pole relay which disconnects the normal

mains lighting ballast from the lamp when the monitored 230/240 volt

mains supply is disconnected

l

A delayed energy relay prevents the automatic protection circuit of the

electronic ballast sensing an open circuit condition, in emergency test

mode, thus enabling the lamp(s) to restrike without having to re-set

the switched supply

l

Electrical connections are made via screw terminals

l

Remote boxes available where integral mount is not possible

Specifications

l

220 – 240V AC, 50Hz

l

Changeover voltage in compliance with BS EN 60598.2.22

l

Input voltage range

50 volt systems: 45 – 55V

110 volt systems: 99 – 121V

l

Weight: 0.5kg

l

Zinc coated steel enclosure

Order codes

MDG50

Conversion module suitable for

4 – 100W fluorescent, 50V AC/DC

MDG110

Conversion module suitable for

4 – 100W fluorescent, 110V AC/DC

For 24 volt AC/DC conversion

modules, please contact our Sales

Department.

Dimensions

230mm x 42.5mm x 29mm

CE marking & warranty

A modified luminaire must be

compliant with the Electro-

Magnetic Compatibility (EMC)

and Low Voltage (LV) Directives,

and carry a CE mark to signify the

compliance.

The company modifying the

general luminaire is legally

responsible for the re-certification

of the complete unit after

modification.

In addition, the warranty provided

by the mains manufacturer will be

invalidated by the modifications.

Conversion service

Emergi-Lite offers a specialist

conversion service backed by the

highest level of expertise, from a

number of strategic Conversion

Centres in the UK.

Emergi-Lite is registered under

ICEL1004 for luminaire conversion.

Specifying the conversion service

to be performed by Emergi-

Lite ensures full compliance. In

addition, the warranty provided

by the mains manufacturer is

taken over by Emergi-Lite and

provides complete peace of mind.

Note: Luminaires to be converted

to emergency must themselves

carry a CE mark to be considered

suitable for conversion.

AC/DC conversion modules