Lighting Control Catalogue

SLAT TRACKING

The “slat tracking” function ensures that the sunblind slats automatically adjust to the position of the sun. In this way, the diffuse

daylight that shines through the blinds can be used. At the same time, the proportion of artificial light can be reduced, the “slat

tracking” function makes lighting energy savings of 10 to 13 percent possible.

INTERACTION BETWEEN SLAT TRACKING AND CONSTANT LIGHT CONTROL

An integrated system permits functions such as slat tracking and constant light control to be used together and in coordination. This

combination is especially advisable in rooms with a good supply of daylight. The savings here can be up to 30 percent.

INTEGRATED ROOMAUTOMATION SYSTEM

A precondition for the optimal effectiveness of all functions is an integrated room automation system, in which the different

systems such as heating, cooling or glare shield work in unison. In an integrated room automation system, the sensors provide the

information for all the systems, while actuators and the lighting, heating, and cooling systems, provide simultaneous support.

PLANNING AND CONFIGURATIONOF AN ENERGY SAVING ROOMAUTOMATION SYSTEM

The planning and configuration of an energy saving room automation system is simplified by the fact that the room automation

system functions conform to the Lonmark profiles used around the world. With this system, room automation functions can be

described clearly and comprehensively.

Once the desired room automation functions have been selected, the savings potential of the particular room automation solution

can be determined, and the chosen solution can be configured with devices.

Functions for saving lighting energy

Room Automation Functions

Savings

Positive factors

Constant light control

(presence-dependent, dimmed)

35 - 50%

- good daylight supply

- high lighting levels (>300lux)

- particularly efficient with slat control

Presence and brightness-dependent lighting control

(switched)

25 - 45%

- good daylight supply

- high lighting levels

Automatic sun protection system

5 - 8%

- good daylight supply

Slat adjustment

10 - 13%

- good daylight supply

- particularly efficient with constant light control

Automatic lighting or staircase lighting

No information

- low presence levels (e.g. corridors)