Due to Link-Power-technology, both data and the supply voltage for the control electronics can be transmitted via the LON
network. Particularly, if the I/O modules are applied peripherally the complexity of cabling is minimised. LPT devices can be
operated in combination with FTT devices in one subnet, but then they require an extra LON Power Supply
The ”DR-S” product line includes, in addition to the DALI Controllers, four I/O modules with the following characteristics:
•
Four resp. eight outputs and the same number of inputs for consumer loads and drives
•
Status LED for every input and output
•
Manual operation
•
Pluggable screw-type terminals
•
Free Topology Transceiver (FTT)
•
230 V supply voltage
•
Configurable reaction of the outputs to power-down and power-up/reset
Conventional push buttons are normally connected to the digital inputs to operate the consumer loads at the outputs. Apart
from that, the digital inputs can be used for floating contacts, e.g. of motion detectors, photo-electric lighting controllers,
or thermostats, independently of the outputs. The contact current is approx. 10 mA. The contact voltage of about 24 V is
generated by the device itself, so that no external power supply unit is required. Every input status, as well as the output
states, is indicated by a status LED. Every output can be operated manually, using the push buttons on top of the casing.
All cables can be connected to the device using pluggable screw-type terminals. The REG-S modules are some of the few
LON actuators that provide the opportunity to configure the outputs’ reaction to power-down as well as to power-up/reset.