Power supplies and transformers
1
Power supplies for DC control circuits
Regulated switch mode power supplies
Phaseo Modular range
Technical characteristics
Power supply type
ABL 8MEM05040
ABL 8MEM12020
Certifications
cULus 508, cCSAus (CSA22.2 n950-1), TUV EN 60950-1,
e
, C-Tick
Conformity to standards
Safety
IEC/EN 60950-1, SELV
EMC
IEC/EN 61000-6-2, EN 61000-6-3, IEC/EN 61204-3, EN 55022 Class B
Input circuit
LED indication
No
Input values
Nominal voltage
V
100…240
a
Limit voltage
V
85…264 V
a
120…250 V
c
(1)
Current consumption
A
0.55 (100 V
a
)
0.35 (240 V
a
)
0.6 (100 V
a
)
0.35 (240 V
a
)
Permissible frequencies
Hz
47…63
Maximum inrush current
A
20
Power factor
> 0.5
Efficiency at nominal load
> 75%
> 80%
Dissipated power at nominal
load
W
6.7
6.2
Output circuit
LED indication
Green LED
Nominal output values
Voltage U
OUT
V
5
c
12...15
c
Current
A
4
2.1
Power
W
20
25
Precision
Output voltage
V
Adjustable from 4.75 to 6.25
Adjustable from 11.4 to 15
Line and load regulation
± 3%
Residual ripple - noise
mV
250
Holding time
for I max
U
IN
min
ms
u
10
Protection
Against short-circuits
Permanent
Against undervoltages
–
Thermal
–
Operating and environmental characteristics
Connections
Input
mm
2
2 x 0.14…2.5 screw terminals (26…14 AWG)
Output
mm
2
4 x 0.14…2.5 screw terminals (26…14 AWG)
Mounting
On
5
rail, 35 x 7.5 mm and 35 x 15 mm or on panel (2 x
Ø
4 mm)
Operating position
On vertical plane
Vertical
Connections
Series
Possible, see page 69
Parallel
Possible, see page 69
Environment
Operating temperature
°C
- 25…+ 70 (derating from 55°C, see page 69)
Storage temperature
°C
- 40…+ 70
Maximum relative humidity
90% during operation
95% in storage
Degree of protection
IP 20 conforming to IEC/EN 60529
Vibration acc. to IEC/EN 61131-2
3...11.9 Hz amplitude 3.5 mm and 11.9 -150 Hz acceleration 2 g
Protection class
According to VDE 0106 1
Class II
Dielectric strength
50 Hz for 1 min
Input/output
V
rms
3000
a
Input fuse incorporated
Yes (not interchangeable)
Emissions
according to EN 61000-6-3
EN 50081-1 (generic)
Radiation
EN 55022 Class B
Conducted on the power line
EN 55022 Class B
Harmonic currents
IEC/EN 61000-3-2
Immunity
according to EN 61000-6-2
IEC 61000-6-2 (generic)
Electrostatic discharge
IEC/EN 61000-4-2 (6 kV contact/8 kV air)
Radiated electromagnetic fields
IEC/EN 61000-4-3 level 3
(10 V/m)
Induced electromagnetic fields
IEC/EN 61000-4-6 level 3 (10 V/m)
Rapid transients
IEC 61000-4-4 (4 kV)
Surges
IEC/EN 61000-4-5 (1 kV)
Primary outages
IEC 61000-4-11 (voltage dips and interruptions)
(1) The certifications cULus 508, cCSAus, TUV 60950-1 are not valid for DC input voltages.
Description:
page 66
References:
page 71
Dimensions:
page 71
Schemes:
page 71
Characteristics
(continued)
1
1
2
3
4
5
6
7
8
9
10