62

Analogue interfaces

Zelio Analog

4

Converters for thermocouples and Pt100 probes

Voltage/current converters

Environment characteristics

Converter types

RMT J/K

ppppp

, RMP

ppppp

, RMC

ppppp

Conforming to standards

IEC 60947-1, IEC 60584-1 (IEC 60751, DIN 43760 for RMP

pppp

)

Product certifications

UL, CSA, GL,

e

Degree of protection

Housing

IP 50

Terminal block

IP 20

Flame resistance

°C

850 conforming to UL, IEC 60695-2-1

Shock resistance

50 gn/11 ms conforming to IEC 68-2-27

Vibration resistance

5 gn (10...100 Hz) conforming to IEC 68-2-6

Immunity to EMC

Resistance to electrostatic discharge

kV

Level 3: 8 (air), 6 (contact) conforming to IEC 1000-4-2

Immunity to fast transient currents

kV

On the power supply: 2; on the input-output: 1 conforming to IEC 1004-4

Surge withstand

kV

0.5 - waves 1.2/50 µs; 0.5 J conforming to IEC 1000-4-5

Disturbance

Radiated/conducted

CISPR11 and CISPR22 Group 1- Class B

Insulation voltage

kV

2

Ambient air temperature around the device

Storage

°C

-40...85 (-40...185 °F)

Operation

°C

Mounted side-by-side: 0...50 (32...122 °F); 2 cm spacing: 0...60 (32...140 °F)

Degree of pollution

2 conforming to IEC 60664-1

Mounting

35 mm DIN rail, clip-on or fixed on mounting plate

Connection

mm

2

2 x 1.5 or 1 x 2.5 cable

Tightening torque

Nm

0.6...1.1

Specific characteristics

Types of converter for thermocouples

RMT J40BD RMT J60BD RMT J80BD RMT K80BD RMT K90BD

Input types

Thermocouple type to IEC 60584

J (Fe-CuNi)

K (Ni-CrNi)

Temperature range

°C

0...150

0...300

0...600

0...600

0...1200

°F

32...302

32...572

32...1112

32...1112

32...2192

Analogue output switchable to voltage or current

Voltage

Range

V

0...10

Minimum impedance of load

k

W

100

Current

Range

mA

0...20 ; 4...20

Maximum impedance of load

W

500

Built-in protection

Reverse polarity, overvoltage (± 30 V) and short-circuit

Safety

Output state when no inputs are wired

or when input wire broken

Output predetermined according to type of output selected:

voltage = - 13 V

current = 0 mA

Supply

Voltage

Rated

c

V

24 ± 20 %, non isolated

Maximum current

consumption

For voltage output

mA

40

For current output

mA

60

Built-in protection

Reverse polarity

Signalling

Green LED (power on)

Measurements

Accuracy

At 20 °C

%

± 1 of the full scale value

± 10 of the full-scale value (in an environment subject to electromagnetic interference

of 10 V/m)

Repeat accuracy

At 20 °C

%

± 0.25 of the full scale value

At 60 °C

%

± 0.8 of the full scale value

Temperature coefficient

ppm/°C

200 (0.02 %)

Cold junction compensation

Built-in, cold junction measurement: 0 to 60 °C (0...140 °F)

Presentation :

pages 60 and 61

References :

page 64

Dimensions :

page 65

Schemes :

page 65

Characteristics

4

1

2

3

4

5

6

7

8

9

10