67
Power supplies and transformers
1
Power supplies for DC control circuits
Regulated switch mode power supplies
Phaseo Modular range
Technical characteristics
Power supply type
ABL 8MEM24003 ABL 8MEM24006 ABL 8MEM24012 ABL 7RM24025
Certifications
cULus 508, cCSAus (CSA22.2 n950-1), TUV 60950-1,
e
,
C-Tick
cULus, CSA, C-Tick
TUV 60950-1,
e
Conformity to standards
Safety
IEC/EN 60950-1, SELV
EMC
IEC/EN 61000-6-2, EN 61000-6-3, IEC/EN 61204-3, EN 55022 Class B
Input circuit
LED indication
No
Input values
Nominal voltage
V
100…240
a
Limit voltage
V
85…264
a
120…250
c
(1)
85…264
a
Current consumption
A
0.25 (100 V
a
)
0.18 (240 V
a
)
0.4 (100 V
a
)
0.25 (240 V
a
)
0.65 (100 V
a
)
0.4 (240 V
a
)
1.2 (120 V
a
)
0.7 (240 V
a
)
Permissible frequencies
Hz
47…63
Maximum inrush current
A
20
90 for 1 ms
Power factor
> 0.5
Efficiency at nominal load
> 78%
> 80%
> 82%
> 84%
Dissipated power at nominal
load
W
2
3.8
6.6
11.4
Output circuit
LED indication
Green LED
Nominal output values
Voltage U
OUT
V
24
c
Current
A
0.3
0.6
1.2
2.5
Power
W
7
15
30
60
Precision
Output voltage
V
Adjustable from 22.8 to 28.8
Line and load regulation
± 3%
Residual ripple - noise
mV
250
200
Holding time
for I max.
U
IN
=100 V
a
ms
u
10
U
IN
=230 V
a
ms
u
150
Protection
Against short-circuits
Permanent
Against undervoltages
V
–
< 19
Thermal
Yes
–
Operating and environmental characteristics
Connections
Input
mm
2
2 x 0.14…2.5 screw terminals (26…14 AWG)
Output
mm
2
2 x 0.14…2.5 screw terminals
(26…14 AWG)
4 x 0.14…2.5 screw terminals
(26…14 AWG)
Mounting
On
5
rail, 35 x 7.5 mm and 35 x 15 mm or on panel (2 x
Ø
4 mm)
Operating position
On vertical plane
Vertical
Connections
Series
Possible, see page 69
Parallel
Possible, see page 69
Environment
Operating temperature
°C
- 25…+ 70 (derating from 55°C, see page 69)
- 25…+ 55
Storage temperature
°C
- 40…+ 70
Relative humidity
90% during operation
95% in storage
Degree of protection
IP 20 conforming to IEC/EN 60529
Vibration acc. to IEC/EN 61131-2
3...11.9 Hz amplitude 3.5 mm and 11.9 -150 Hz acceleration 2 g
Protection class
According to VDE 0106 1
Class II
Dielectric strength
50 Hz for 1 min
Input/output
V
rms
3000
a
Input fuse incorporated
Yes (not interchangeable)
Emissions
according to EN 61000-6-3
EN 50081-1 (generic)
Radiation
EN 55022 Class B
Conducted on the power line
EN 55022 Class B
Harmonic currents
IEC/EN 61000-3-2
Immunity
according to IEC/EN 61000-6-2
IEC 61000-6-2 (generic)
Electrostatic discharge
IEC/EN 61000-4-2 (6 kV contact/8 kV air)
IEC/EN 61000-4-2
(4 kV contact/8 kV air)
Radiated electromagnetic fields
IEC/EN 61000-4-3 level 3
(10 V/m)
Induced electromagnetic fields
IEC/EN 61000-4-6 level 3 (10 V/m)
Rapid transients
IEC 61000-4-4 (4 kV)
Surges
IEC/EN 61000-4-5 (1 kV)
Primary outages
IEC 61000-4-11 (voltage dips and interruptions)
(1) The certifications cULus 508, cCSAus, TUV 60950-1 are not valid for DC input voltages.
Presentation:
page 66
References:
page 71
Dimensions:
page 71
Schemes:
page 71
Characteristics
1
1
2
3
4
5
6
7
8
9
10