Table of Contents Table of Contents
Previous Page  64 / 73 Next Page
Information
Show Menu
Previous Page 64 / 73 Next Page
Page Background

63

Analogue interfaces

Zelio Analog

4

Converters for thermocouples and Pt100 probes

Voltage/current converters

Specific characteristics

(continued)

Types of converter for Pt100 probes

RMP T10/13BD RMP T20/23BD RMP T30/33BD RMP T50/53BD RMP T70/73BD

Input types

Probe type

Pt100 - IEC 60751; DIN 43760 (2, 3, 4-wire)

Temperature range

°C

- 40...40

- 100...100

0...100

0...250

0...500

°F

- 40...104

- 148...212

32...212

32...482

32...932

Analogue output

Output selection

0...10 V/0...20 mA, 4...20 mA switchable for RMP T

p

0BD

0...10 V or 4...20 mA for RMP T

p

3BD

Voltage

Minimum impedance of load

k

W

100

Current

Maximum impedance of load

W

500

Built-in protection

Reverse polarity, overvoltage (± 30 V) and short-circuit

Safety

Output state when no inputs are

wired or when input wire broken

Output predetermined according to type of output selected:

voltage = ± 13 V

current = 0 mA

Supply

Voltage

Rated

c

V

24 ± 20 %, non isolated

Maximum current

consumption

For voltage output

mA

40

For current output

mA

60

Built-in protection

Reverse polarity

Signalling

Green LED (power on)

Measurements

Accuracy

At 20 °C

%

± 0.5 (3, 4-wire connection) of the full scale value

± 1 (2-wire connection) of the full scale value

± 10 of the full-scale value (in an environment subject to electromagnetic interference

of 10 V/m)

Repeat accuracy

At 20 °C

%

± 0.2 of the full scale value

At 60 °C

%

± 0.6 of the full scale value

Temperature coefficient

ppm/°C

150 (0.015 %)

Connection in 2-wire mode

Maximum resistance of cable

m

W

200

Specific characteristics

Types of voltage/current converters

RMC N22BD

RMC L55BD RMC V60BD RMC A61BD

Input types

Voltage

V

c

0...10

c

0...10, ±10

0...50; 0...300;

0...500

c

or

a

50/60 Hz

Current

mA

4...20

0...20 ; 4...20

A

0...1.5; 0...5; 0...15

c

or

a

50/60 Hz

Analogue output

Output selection

By cabling

Switchable

Switchable

By cabling

Voltage

Range

V

0...10

0...10; ± 10

0...10

0...10

Minimum impedance of load

k

W

100

Current

Range

mA

4...20

0...20; 4...20

0...20; 4...20

0...20 4...20

Maximum impedance of load

W

500

Built-in protection

Reverse polarity, overvoltage (± 30 V) and short-circuit

Safety

Output state when no inputs are

wired or when input wire broken

Output predetermined according to type of output selected:

voltage:

< 0 V

current:

< 4 mA

voltage:

- 10…+ 10 V: -10 V

0…+ 10 V : 0 V

current:

0…20 mA : 0 mA

4…20 mA : 4 mA

voltage: < 0 V

current:

0…20 mA : 0 mA

4…20 mA : < 4 mA

Supply

Voltage

Rated

V

c

24 ± 20 %

non isolated

c

24 ± 20 % isolated (1.5 kV)

Maximum current

consumption

For voltage output

mA

40

70

For current output

mA

60

90

Built-in protection

Reverse polarity

Signalling

Green LED (power on)

Measurements

Accuracy

At 20 °C

%

± 1 of the full scale value

± 10 of the full-scale value (in an

environment subject to electromagnetic

interference of 10 V/m)

± 5 of the full scale value

± 10 of the full-scale value (in an

environment subject to electromagnetic

interference of 10 V/m)

Repeat accuracy

At 20 °C

%

± 0.2 of the full scale value

At 60 °C

%

± 0.6 of the full scale value

Temperature coefficient

ppm/°C

200 (0.02 %)

0...1.5 A: 500 (0.05 %)

0...5 A: 1000 (0.1 %)

0...15 A: 2000 (0.2 %)

Presentation :

pages 60 and 61

References :

page 64

Dimensions :

page 65

Schemes :

page 65

Characteristics

(continued)

4

1

2

3

4

5

6

7

8

9

10