52

Characteristics

1

Communication interface environment characteristics

Interface type

SR2 COM01

SR2 MOD02

Product certifications

UL, CSA, C-Tick, GOST

UL, CSA, IC, PTCRB, FCC part 15

standards, GOST (pending)

Conformity with the low

voltage directive

Conforming to 2006/95/EC

EN (IEC) 61131-2 (open equipment)

EN (IEC) 60950-1

Conformity with the

EMC directive

Conforming to 2004/108/EC

EN (IEC) 61131-2 (Zone B)

EN (IEC) 61000-6-2, EN (IEC) 61000-6-3

and EN (IEC) 61000-6-4

EN 301 489-1

Conformity to the

R and TTE directive

Conforming to 1999/5/EC

ETSI EN 301 489-7, EN 301 419-1,

EN 301 511

Degree of protection

Conforming to IEC/EN 60529

IP 20 (terminal block), IP 40 (front panel) IP 31

Overvoltage category

3 (conforming to IEC/EN 60664-1)

2 (conforming to IEC/EN 60950-1)

Degree of pollution

2 (conforming to IEC/EN 61131-2)

2 (conforming to IEC/EN 60950-1)

Ambient air temperature

around the device

conforming to IEC/EN 60028-2-1

and IEC/EN 60068-2-2

Operation

°C

- 20...+ 55 (+ 40 in non-ventilated

enclosure)

- 20...+ 55

Storage

°C

- 40...+ 70

- 40...+ 70

Maximum relative humidity

conforming to

IEC/EN 60068-2-30

Operation

95% without condensation or dripping

water

95 % at 55°C without condensation

Storage

95% without condensation or dripping

water

30 %…95 % without condensation

Maximum operating altitude

Operation

m

2000

2000

Transport

m

3048

3048

Mechanical resistance

Immunity to vibration

IEC/EN 60068-2-6, test Fc

IEC/EN 60068-2-6, test Fc

Immunity to free fall

EN (IEC) 60068-2-32

Resistance to

electrostatic discharge

Immunity to electrostatic

discharge

IEC/EN 61000-4-2, level 3

IEC/EN 61000-4-2

- contact: level 2

- air: level 3

Resistance to HF interference

(immunity)

Immunity to electromagnetic

radiated fields

IEC/EN 61000-4-3

IEC/EN 61000-4-3

Immunity to fast transients in

bursts

IEC/EN 61000-4-4, level 3

IEC/EN 61000-4-4, level 1

Immunity to shock waves

IEC/EN 61000-4-5

Radio frequency in common

mode

IEC/EN 61000-4-6, level 3

IEC/EN 61000-4-6, level 2

Immunity to damped oscillation

waves

IEC/EN 61000-4-12

Conducted and

radiated emissions

Conforming to EN 55022/11

(Group 1)

Class B

Class B

Screw terminals

connection capacity

Flexible cable with cable end

mm

2

1 conductor: 0.25...2.5,

cable: AWG 24...AWG 14

2 conductors: 0.25...0.75,

cable: AWG 24...AWG 18

Semi-solid cable

mm

2

1 conductor: 0.2...2.5,

cable: AWG 25...AWG 14

Solid cable

mm

2

1 conductor: 0.2...2.5,

cable: AWG 25...AWG 14

2 conductors: 0.2...1.5,

cable: AWG 24...AWG 16

Tightening torque

N.m

0.5 (tightened using Ø 3.5 mm

screwdriver)

Supply characteristics

Interface type

SR2 COM01

SR2 MOD01

SR2 MOD02

Nominal voltage

V

c

12…24

Voltage limits

V

c

10…28.8

c

10…30

c

5.5…32

Maximum ripple

5 %

Nominal current

c

12 V

mA

30

140

165

c

24 V

mA

30

70

87

Current peak on power-up

mA

550

9600

2100 on 5.5 V

Power dissipated

W

1.1

1.7

2.1

Micro-breaks

Permissible duration

1 ms, repeated 20 times –

Protection

Integrated

Against reversed polarity –

To be provided externally

A

1 A fuse

Supplied with 2.5 A fuse

Presentation, description :

pages 48 and 49

Functions, setting-up

pages 50 and 51

References :

page 54

Dimensions :

page 55

Connections :

pages 56 and 57

Zelio Logic smart relays

1

Modem communication interface

1

2

3

4

5

6

7

8

9

10