Page Background

D-8

Additional information

The energy management

with Prisma P

Presentation

+

24VDC

13

O1

I1

I2

I3

I4

I5

I6

C

C

C

14

2324

33

34

T1T2

O2

O3

A1

Vers coffret

individuel

FDM128 switchboard display

It can be connected to a Micrologic COM option

(BCM ULP via IFE). It uses the sensors and

processing capacity of the Micrologic control unit. It

is easy to use and requires no special software or

settings.

The FDM128 is a large display, but requires very

little depth. The anti-glare graphic screen is backlit

for very easy reading even under poor ambient

lighting and at sharp angles.

Switch Ethernet

Ethernet switch , 5 copper ports

Communication port protocol : Ethernet TCP/IP

Ethernet port : 10BASE-T/100BASE-TX - 5 ports

copper cables

Max number of cascading switches : unlimited

24 V DC power supply

An external 24 V DC power supply is required for

installations with communication,

whatever the type of trip unit.

A single external 24 V DC supply may be used for

the entire switchboard.

The required characteristics are:

b

output voltage: 24 V DC ±5 %

b

ripple: ±1 %.

b

overvoltage category: OVC IV -

as per IEC 60947-1.

I/O application module

The I/O (Input/Output) application module for LV

breaker is part of an ULP system with built-in

functionalities and applications to enhance the

application needs.

The ULP system architecture can be built without

any restrictions using the wide range of circuit

breakers.

The I/O application module is compliant with the

ULP system specifications.

Two IO application modules can be connected in the

same ULP network. The ranges of LV circuit-

breakers enhanced by the IO are :

b

Masterpact NW

b

Masterpact NT

b

Compact NS 1600b-3200 and NS630b-1600

b

Compact NSX100-630