![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0244.jpg)
D-8
Additional information
The energy management
with Prisma P
Presentation
+
24VDC
13
O1
I1
I2
I3
I4
I5
I6
C
C
C
14
2324
33
34
T1T2
O2
O3
A1
Vers coffret
individuel
FDM128 switchboard display
It can be connected to a Micrologic COM option
(BCM ULP via IFE). It uses the sensors and
processing capacity of the Micrologic control unit. It
is easy to use and requires no special software or
settings.
The FDM128 is a large display, but requires very
little depth. The anti-glare graphic screen is backlit
for very easy reading even under poor ambient
lighting and at sharp angles.
Switch Ethernet
Ethernet switch , 5 copper ports
Communication port protocol : Ethernet TCP/IP
Ethernet port : 10BASE-T/100BASE-TX - 5 ports
copper cables
Max number of cascading switches : unlimited
24 V DC power supply
An external 24 V DC power supply is required for
installations with communication,
whatever the type of trip unit.
A single external 24 V DC supply may be used for
the entire switchboard.
The required characteristics are:
b
output voltage: 24 V DC ±5 %
b
ripple: ±1 %.
b
overvoltage category: OVC IV -
as per IEC 60947-1.
I/O application module
The I/O (Input/Output) application module for LV
breaker is part of an ULP system with built-in
functionalities and applications to enhance the
application needs.
The ULP system architecture can be built without
any restrictions using the wide range of circuit
breakers.
The I/O application module is compliant with the
ULP system specifications.
Two IO application modules can be connected in the
same ULP network. The ranges of LV circuit-
breakers enhanced by the IO are :
b
Masterpact NW
b
Masterpact NT
b
Compact NS 1600b-3200 and NS630b-1600
b
Compact NSX100-630