A-66

Installation

Mounting plates are equipped with the power factor

correction modules, made up of a contactor, the

corresponding protection fuses and a set of busbars.

>

>

They are installed in a 650 mm + 150 mm wide

cubicle that is either 400 or 600 mm deep

depending on the depth of the switchboard to

which it will be added.

>

>

Each cubicle can be equipped with up to

5VarplusCan power factor correction Modules

(100kvar) or up to 4 VarplusCan with self power

factor correction Modules (50 kvar), positioned one

above the other.

>

>

The cubicle has a ventilated roof that can be

equipped with one or two fans.

>

>

The door has cut-outs, one for the Varlogic power

factor controller and another in the bottom for a

filter.

Device installation

VarplusCan with self :

>

>

No. of power factor correctionmodules per cubicle: 4

>

>

Power range (kvar): 200

>

>

Catalogue number:

03979

.

VarplusCan without self :

>

>

No. of power factor correctionmodules per cubicle: 5

>

>

Power range (kvar): 500

>

>

Catalogue number:

03979

.

Others

Power factor correction

equipment

Prisma P cubicles can be used for installation of the new

“VarplusCan” power factor correction modules designed

to improve power system quality and reduce consumption

of reactive energy.

These modules are made up of capacitors, contactors and

special protection against internal faults.

The power factor correction modules are installed

horizontally in a cubicle.

It is necessary to select each devices to create the power

factor correction module according to the “Panelbuilder

guide of Power Factor correction” number

FCED111008EN.

The busbars are supplied by a protection device installed

in an adjacent cubicle.

Special Prisma P cubicles are used for power factor

correction, given the temperature rise inside the cubicles.

They comply with and are tested according to standard

IEC 61439-1 et 2.

DD385374.EPS

Presentation

DD385395.eps

DD385437.eps

Standard cubicle

supplied via the bottom.

Cubicle with a 300 mm wide

compartment for incoming

cables via the top.

DD385373.eps

Functional system

Functional units