![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0120.jpg)
A-66
Installation
Mounting plates are equipped with the power factor
correction modules, made up of a contactor, the
corresponding protection fuses and a set of busbars.
>
>
They are installed in a 650 mm + 150 mm wide
cubicle that is either 400 or 600 mm deep
depending on the depth of the switchboard to
which it will be added.
>
>
Each cubicle can be equipped with up to
5VarplusCan power factor correction Modules
(100kvar) or up to 4 VarplusCan with self power
factor correction Modules (50 kvar), positioned one
above the other.
>
>
The cubicle has a ventilated roof that can be
equipped with one or two fans.
>
>
The door has cut-outs, one for the Varlogic power
factor controller and another in the bottom for a
filter.
Device installation
VarplusCan with self :
>
>
No. of power factor correctionmodules per cubicle: 4
>
>
Power range (kvar): 200
>
>
Catalogue number:
03979
.
VarplusCan without self :
>
>
No. of power factor correctionmodules per cubicle: 5
>
>
Power range (kvar): 500
>
>
Catalogue number:
03979
.
Others
Power factor correction
equipment
Prisma P cubicles can be used for installation of the new
“VarplusCan” power factor correction modules designed
to improve power system quality and reduce consumption
of reactive energy.
These modules are made up of capacitors, contactors and
special protection against internal faults.
The power factor correction modules are installed
horizontally in a cubicle.
It is necessary to select each devices to create the power
factor correction module according to the “Panelbuilder
guide of Power Factor correction” number
FCED111008EN.
The busbars are supplied by a protection device installed
in an adjacent cubicle.
Special Prisma P cubicles are used for power factor
correction, given the temperature rise inside the cubicles.
They comply with and are tested according to standard
IEC 61439-1 et 2.
DD385374.EPS
Presentation
DD385395.eps
DD385437.eps
Standard cubicle
supplied via the bottom.
Cubicle with a 300 mm wide
compartment for incoming
cables via the top.
DD385373.eps
Functional system
Functional units