B-6
Wiring of voltage releases
During pick-up, the power consumed is approximately 150 to 200 VA. For low control
voltages (12, 24, 48 V), maximum cable lengths are imposed by the voltage and the
cross-sectional area of cables.
Recommended maximum cable lengths (meter).
12 V
24 V
48 V
2,5 mm
2
1,5 mm
2
2,5 mm
2
1,5 mm
2
2,5 mm
2
1,5 mm
2
MN U source 100 % –
–
58
35
280
165
U source 85 % –
–
16
10
75
45
MX-XF U source 100 % 21
12
115
70
550
330
U source 85 % 10
6
75
44
350
210
Note:
the indicated length is that of each of the two wires.
24 V DC power-supply module
External 24 V DC power-supply module for Micrologic (F1-, F2+)
do not connect the positive terminal (F2+) to earth
b
b
the negative terminal (F1-) can be connected to earth, except in IT systems
b
b
a number of Micrologic control units and M6C modules can be connected to the
b
b
same 24 V DC power supply (the consumption of a Micrologic control unit or an M6C
module is approximately 100 mA)
do not connect any devices other than a Micrologic control unit or an M6C module
b
b
if voltage > 480 V AC or in an environment with a high level of electromagnetic
disturbance
the maximum length for each conductor is ten metres. For greater distances, it is
b
b
advised to twist the supply wires together
the 24 V DC supply wires must cross the power cables perpendicularly. If this is
b
b
difficult, it is advised to twist the supply wires together
the technical characteristics of the external 24 V DC power-supply module for
b
b
Micrologic control units are indicated on
page A-27
.
Communication bus
do not connect the positive terminal (E1) to earth
b
b
the negative terminal (E2) can be connected to earth
b
b
a number of “device” or “chassis” communication modules can be connected to
b
b
the same 24 V DC power supply (the consumption of each module is approximately
30 mA).
Note:
wiring of ZSI: it is recommended to use twisted shielded cable. The shield must be
connected to earth at both ends.
Control wiring