Page Background

B-5

Installation

recommendations

Door interlock VPEC

Mounted on the right or left-hand side of the chassis,

this device inhibits opening of the cubicle door when

the circuit breaker is in “connected” or “test” position.

It the breaker is put in the “connected” position with the

door open, the door may be closed without having to

disconnect the circuit breaker.

DB117044

Dimensions (mm)

Type

(1)

(2)

NT08-16 (3P)

135

168

NT08-16 (4P)

205

168

NW08-40 (3P)

215

215

NW08-40 (4P)

330

215

NW40b-63 (3P)

660

215

NW40b-63 (4P)

775

215

Dimensions (mm)

Breaker in “connected”

or “test” position

Door cannot be opened

Breaker in “disconnected”

position

Door can be opened

DB103819

DB102194

Type

(1)

(2)

NT

5

23

NW

83

103

Cable-type door interlock IPA

This option prevents door opening when the circuit

breaker is closed and prevents circuit breaker closing

when the door is open.

For this, a special plate associated with a lock and a

cable is mounted on the right side of the circuit breaker.

With this interlock installed, the source changeover

function cannot be implemented.

DB101445

DB101446

Note:

the door interlock can either be mounted on the right side

or the left side of the breaker.

: datum.

Catch not supplied

Door interlock catch

version: 8.3