B-5
Installation
recommendations
Door interlock VPEC
Mounted on the right or left-hand side of the chassis,
this device inhibits opening of the cubicle door when
the circuit breaker is in “connected” or “test” position.
It the breaker is put in the “connected” position with the
door open, the door may be closed without having to
disconnect the circuit breaker.
DB117044
Dimensions (mm)
Type
(1)
(2)
NT08-16 (3P)
135
168
NT08-16 (4P)
205
168
NW08-40 (3P)
215
215
NW08-40 (4P)
330
215
NW40b-63 (3P)
660
215
NW40b-63 (4P)
775
215
Dimensions (mm)
Breaker in “connected”
or “test” position
Door cannot be opened
Breaker in “disconnected”
position
Door can be opened
DB103819
DB102194
Type
(1)
(2)
NT
5
23
NW
83
103
Cable-type door interlock IPA
This option prevents door opening when the circuit
breaker is closed and prevents circuit breaker closing
when the door is open.
For this, a special plate associated with a lock and a
cable is mounted on the right side of the circuit breaker.
With this interlock installed, the source changeover
function cannot be implemented.
DB101445
DB101446
Note:
the door interlock can either be mounted on the right side
or the left side of the breaker.
: datum.
Catch not supplied
Door interlock catch
version: 8.3
207E3300.indd