Page Background

A-20

Functions

and characteristics

Power Meter functions

Micrologic A/E/P/H control unit

with COM option (BCM ULP)

In addition to protection functions, Micrologic A/E/P/H

control units offer all the functions of Power Meter

products as well as operating-assistance for the circuit

breaker.

Micrologic A/E/P/H measurement functions are made possible by Micrologic

intelligence and the accuracy of the sensors. They are handled by a microprocessor

that operates independent of protection functions.

Display

..................................................................

FDM121 display unit

The FDM121 switchboard display unit can be connected to a Micrologic COM option

(BCM ULP) using a breaker ULP cord to display all measurements on a screen. The

result is a veritable 96 x 96 mm Power Meter.

In addition to the information displayed on the Micrologic LCD, the FDM121 screen

shows demand, power quality and maximeter/minimeter values along with histories

and maintenance indicators.

The FMD121 display unit requires a 24 V DC power supply. The COM option (BCM

ULP) unit is supplied by the same power supply via the breaker ULP cord connecting

it to the FDM121.

Measurements

......................................................

Instantaneous rms measurements

The Micrologic continuously display the RMS value of the highest current of the three

phases and neutral (Imax). The navigation buttons can be used to scroll through the

main measurements.

In the event of a fault trip, the trip cause is displayed.

The Micrologic Ameasures phase, neutral, ground fault currents.

The Micrologic E offers voltage, power, Power Factor, measurements in addition to

the measurements provided by Micrologic A.

The Micrologic P/H offer frequency, cos.

j

in addition to the measurements provided

by Micrologic E.

Maximeters / minimeters

Every instantaneous measurement provided by Micrologic A or E can be associated

with a maximeter/minimeter. The maximeters for the highest current of the 3 phases

and neutral, the demand current and power can be reset via the FDM121 display unit

or the communication system.

Energy metering

The Micrologic E/P/H also measures the energy consumed since the last reset of the

meter. The active energy meter can be reset via Micrologic keypad or the FDM121

display unit or the communication system.

Demand and maximum demand values

Micrologic E/P/H also calculates demand current and power values. These

calculations can be made using a block or sliding interval that can be set from 5 to 60

minutes in steps of 1 minute. The window can be synchronised with a signal sent via

the communication system. Whatever the calculation method, the calculated values

can be recovered on a PC via Modbus communication.

Ordinary spreadsheet software can be used to provide trend curves and forecasts

based on this data. They will provide a basis for load shedding and reconnection

operations used to adjust consumption to the subscribed power.

Power quality

Micrologic H calculates power quality indicators taking into account the presence of

harmonics up to the 15th order, including the total harmonic distortion (THD) of

current and voltage.

DB125911

Alarms

Services

ESC

OK

MainMenu

Quick view

Control

Metering

FDM121 display: navigation.

DB112131

I1

I

%

310 A I2

%

315 A

I3

%

302 A IN

%

23 A

ESC

DB112132

ESC

U

1

U

2

U

3

V

4/7

402V

100 120

%

398V

100 120

%

401V

100 120

%

Current.

Voltage.

DB112133

ESC

P

64 kW

Q

38 kVar

S

51 kVA

PQS

DB112134

ESC

Ep

14397 kWh

Eq

8325 kVarh

Es

13035 kVAh

E

Power.

Consumption.

Examples of measurement screens on the FDM121 display

unit.