A-82
Functions and
characteristics
Accessories and auxiliaries
Motor mechanism
PB103372-30
Compact NSX250 with motor mechanism.
When equipped with a
motor-mechanism
module, Compact NSX circuit breakers
feature very high mechanical endurance as well as easy and sure operation:
all circuit-breaker indications and information remain visible and accessible,
b
including trip-unit settings and indications
suitability for isolation is maintained and padlocking remains possible
b
double insulation of the front face.
b
$ VSHFL¿F PRWRU PHFKDQLVP LV UHTXLUHG IRU RSHUDWLRQ YLD WKH FRPPXQLFDWLRQ
function. This
communicating motor mechanism
must be connected to the BSCM
module to receive the opening and closing orders. Operation is identical to that of a
standard motor mechanism.
Applications
Local
b
motor-driven operation, centralised operation, automatic distribution control.
Normal/standby source changeover or switching to a replacement source to
b
ensure availability or optimise energy costs.
Load shedding and reconnection.
b
Sy
b
nchrocoupling.
Operation
The type of operation is selected using the manual/auto mode selection switch (
7
).
A transparent, lead-seal cover controls access to the switch.
Automatic
When the switch is in the "auto" position, the ON/OFF (I/O) buttons and the charging
lever on the mechanism are locked.
Circuit-breaker ON and OFF controlled by two impulse-type or maintained signals.
b
Automatic spring charging following voluntary tripping (by MN or MX), with
b
standard wiring.
Mandatory manual reset following tripping due to an electrical fault.
b
Manual
When the switch is in the "manual" position, the ON/OFF (I/O) buttons may be used.
Amicroswitch linked to the manual position can remote the information.
Circuit-breaker ON and OFF controlled by 2 pushbuttons I/O.
b
Recharging of stored-energy system by pumping the lever 8 times.
b
Padlocking in OFF position.
b
Installation and connections
All installation
¿[HG SOXJ LQ ZLWKGUDZDEOH DQG FRQQHFWLRQ SRVVLELOLWLHV DUH
maintained.
Motor-mechanism module connections are made behind its front cover to integrated
terminals, for cables up to 2.5 mm².
Optional accessories
Keylock
b
for locking in OFF position.
Operations counter for the Compact NSX400/630, indicating the number of ON/
b
OFF cycles. Must be installed on the front of the motor-mechanism module.
Characteristics
Motor mechanism
MT100 to MT630
Response time (ms)
opening
closing
< 600
< 80
Operating frequency
F\FOHV PLQXWH PD[
4
Control voltage (V)
DC
24/30 - 48/60 - 110/130 - 250
AC 50/60 Hz
48 (50 Hz) - 110/130 -
220/240 - 380/440
Consumption
(1)
DC (W)
opening
closing
y
500
y
500
AC (VA)
opening
closing
y
500
y
500
(1)
For NSX100 to NSX250, the inrush current is 2 In for 10 ms.
Electrical endurance
DB111335
dis
c
h
a
rged
0
OFF
OFF
ON
3
1 2
5 6
78
4
1
Position indicator
(positive contact indication)
2
Spring status indicator (charged, discharged)
3
Manual spring-charging lever
4
Keylock device (optional)
Locking device (OFF position), using 1 to 3 padlocks,
shackle diameter 5 to 8 mm, not supplied
5
I (ON) pushbutton
6
O (OFF) pushbutton
7
Manual/auto mode selection switch. The position of this
switch can be indicated remotely.
8
Operation counter (Compact NSX400/630)
DB115690
0.
2
0.
7
1
0.5
0.3
NS100
NS160
NS250
NS400
NS6
3
0
50
40
30
2
0
15
10
6
4
0.1
I/In
Circuit breaker + motor-
mechanism module, in
thousands of operations
(IEC 60947 2), at 440 V.