A-81

SDx and SDTAM modules for Micrologic

SDx and SDTAM are relay modules with two

static outputs. They send different signals

depending on the type of fault. They may

not be used together.

PB103377-20

SDx relay module with its terminal block.

PB103376-20

SDTAM relay module with its terminal block.

SDx module

The SDx module remotes the trip or alarm conditions of Compact NSX circuit

breakers equipped with electronic protection.

The SD2 output, available on all Micrologic trip units, corresponds to the overload-

trip indication.

The SD4 output, available on Micrologic 5 / 6, is assigned to:

overload pre-alarm (Micrologic 5)

b

ground-fault trip indication (Micrologic 6).

b

These two outputs automatically reset when the device is closed (turned ON).

For Micrologic 5 / 6, the SD2 and SD4 outputs can be reprogrammed to be assigned

to other types of tripping or alarm.

Output characteristics

It is possible to assign a function:

latching with a time delay. Return to the initial state occurs at the end of the time

b

delay

permanent latching. In this case, return to the initial state takes place via the

b

communication function.

Static outputs: 24 to 415 V AC / V DC; 80 mAmax.

SDTAM module

7KH 6'7$0 PRGXOH LV VSHFL¿FDOO\ IRU WKH PRWRU SURWHFWLRQ 0LFURORJLF WULS XQLWV

2.2 M, 2.3 M and 6.2 E-M, 6.3 E-M.

The SDTAM module, linked to the contactor controller, opens the contactor when an

overload or other motor fault occurs, thus avoiding opening of the circuit breaker.

Micrologic 2 M

The SD4 output opens the contactor 400 ms before normal circuit-breaker opening

in the following cases:

overload (long-time protection for the trip class)

b

phase unbalance or phase loss.

b

The SD2 output serves to memorise contactor opening by SDTAM.

Micrologic 6 E-M

The SD4 output opens the contactor 400 ms before normal circuit-breaker opening

in the following cases:

overload (long-time protection for the trip class)

b

phase unbalance or phase loss

b

locked rotor

b

underload (undercurrent protection)

b

long start.

b

The SD2 output serves to memorise contactor opening by SDTAM.

Output characteristics

Output reset can be:

manual by a pushbutton included in the wiring diagram

b

automatic after an ad

j

ustable time delay (1 to 15 minutes) to take into account the

b

motor-cooling time.

Static outputs: 24 to 415 V AC / V DC; 80 mAmax.

DB115603

a

(+)

2

4 to 415

V

a

(-)

S

D4

S

D

2

S

D3

SD

x

Q

S

D1

S

DT

or output 1

P

A

L Ir

or

S

DG

or output

2

DB115604

a

(+)

2

4 to 415

V

a

(-)

SDTAM

A

uto reset (

m

n)

OFF

1

14

15

2

12

4

10

6 8

S

D1

S

D4

S

D

2

S

D3

S

DT

M

a

nu

a

l

reset

K

A

I

K

A

I

KMI

KMI

Q

KMI

Closin

g

order

Openin

g

order

SDx wiring diagram.

SDTAM wiring diagram with contactor control.

559E1860.indd

version: 1.0