A-87

Insulation monitoring module

This module detects and indicates an insulation drop on a load circuit (TN-S or TT

systems).

Operation is identical to that of a Vigi module, but without circuit-breaker tripping.

Indication by a red LED in front.

$Q DX[LOLDU\ FRQWDFW PD\ EH LQVWDOOHG IRU UHPRWH LQVXODWLRQ GURS LQGLFDWLRQV

When insulation drops below a minimum, user-set threshold, the LED goes on and

WKH DX[LOLDU\ FRQWDFW VZLWFKHV 7KH IDXOW LQGLFDWLRQ FDQQRW EH FDQFHOOHG H[FHSW E\

pressing the manual reset button.

Installation

The module is installed directly on the downstream circuit-breaker terminals.

b

Degree of protection IP40, IK04.

b

Double insulation of the front face.

b

Electrical characteristics

Settings: 100 - 200 - 500 - 1000 mA

b

Accuracy: -50 +0 %

b

Time delay following insulation drop: 5 to 10 seconds

b

AC-system voltage: 200 to 440 V AC.

b

PB103602-32

Insulation monitoring module.