A-86

Functions and

characteristics

Accessories and auxiliaries

Additional measurement and indication modules

PB103795-36

Voltage-presence indicator.

PB103600-32

Compact NSX with current-transformer module.

PB103601-32

Compact NSX with ammeter module.

Voltage-presence indicator

The indicator detects and indicates that circuit breaker terminals are supplied with

power.

Installation

Mounted in the long or short terminal shields, via the knockouts.

b

May be positioned upstream or downstream of the circuit breaker.

b

Degree of protection IP40, IK04.

b

Not compatible with the motor-mechanism module.

b

Electrical characteristics

Operates on all networks with voltages ranging from 220 to 550 V AC.

Current-transformer module

This module enables direct connection of a measurement device such as an

ammeter or a power meter.

Installation

The module is installed directly on the downstream circuit-breaker terminals.

b

Degree of protection IP40, IK04.

b

Class II insulation between front and the power circuits.

b

Connection to 6 integrated connectors for cables up to 2.5 mm².

b

Electrical characteristics

Current transformer with 5 A secondary winding.

b

Class 3 for the following output-power consumptions:

b

Accuracy:

100 A rating: 1.6 VA

v

150 A rating: 3 VA

v

250 A rating: 5 VA

v

400/600 A rating: 8 VA.

v

Current-transformer module with voltage

measurement outputs

This module enables direct connection of a digital measurement device such as a

Power Meter PM700, PM800, etc. (not supplied).

Installation

The module is installed directly on the downstream circuit-breaker terminals.

b

Degree of protection IP40, IK04.

b

Class II insulation between front and the power circuits.

b

Built-in connectors for cables from 1.5 to 2.5 mm².

b

Electrical characteristics

Rated operational voltage Ue: 530 V

b

Frequencies of measured values: 50...60 Hz

b

Three CTs with 5 A secondary windings for the rated primary current In :

b

class 0.5 to 1 for rated power consumption values at the output:

v

125 A, 150 A and 250 A ratings: class 1 for 1.1 VA

-

400/600 A rating: class 0.5 for 2 VA

-

Connection using a 2.5 mm2 cable up to 2.5 m long.

v

Four voltage measurement outputs including protection with automatic reset.

b

voltage measurement output impedance 3500

v

8

“ PD[LPXP FXUUHQW P$

The voltage measurement outputs are intended only for measurements (1 mA

v

PD[ DQG PD\ QRW EH XVHG WR VXSSO\ WKH

display.

Ammeter and Imax ammeter modules

Ammeter module

Measures and displays (dial-type ammeter) the current of each phase (selection of

phases by 3-position switch in front).

Imax ammeter module

0HDVXUHV DQG GLVSOD\V GLDO W\SH DPPHWHU WKH PD[LPXP FXUUHQW ÀRZLQJ LQ WKH

PLGGOH SKDVH 7KH ,PD[ YDOXH FDQ EH UHVHW RQ WKH IURQW

Installation

Identical for both types of ammeter module.

b

The module is installed directly on the downstream circuit-breaker terminals.

b

The ammeter clips into the module in any of four 90° positions, i.e. it can be

b

installed of devices mounted both vertically and horizontally.

Degree of protection IP40, IK04.

b

Class II insulation between front and the power circuits.

b

Electrical characteristics

Ammeter module: accuracy class 4.5

b