A-32

Functions and characteristics

Compact communication

RSU and RCU utilities

RSU (Remote Setting Utility)

This utility is used to set the protection functions and alarms for each Compact and

Compact NSX device.

After connection to the network and entry of the circuit breaker Modbus address,

the software automatically detects the type of trip unit installed.

There are two possible operating modes.

Off-line with the software disconnected from the

communication network

For each selected circuit breaker, the user can do the following.

Determine the protection settings

The settings are carried out on a screen that shows the front of the trip unit.

The Micrologic setting dials, keypad and screen are simulated for easy use of all

Micrologic setting functions.

Save and duplicate the protection settings

Each configuration created can be saved for subsequent device programming. It can

also be duplicated and used as the basis for programming another circuit breaker.

On-line with the software connected to the network

Similarly, for each selected circuit breaker, the user can do the following.

Display the current settings

The software displays the trip unit and provides access to all settings.

View the corresponding protection curves

A graphic curve module in the software displays the protection curve corresponding

to the settings. It is possible to lay a second curve over the first for discrimination

studies.

Modify settings in a secure manner

There are different levels of security:

b

password: by default, it is the same for all devices, but can be differentiated for

v

each device

locking of the Modbus interface module which must be unlocked before the

v

corresponding device can be set remotely

maximum settings limited by the positions of the two dials on the trip unit.

v

These dials, set by the user, determine the maximum settings that can be made via

the communication system.

Settings are modified by:

b

either direct, on-line setting of the protection settings on the screen

v

or by loading the settings prepared in off-line mode. This is possible only if the

v

positions of the dials allow the new settings.

All manual settings made subsequently on the device have priority.

Program alarms

Up to 12 alarms can be linked to measurements or events.

b

two alarms are predefined and activated automatically:

b

Micrologic 5: overload (Ir)

v

Micrologic 6: overload (Ir) and ground fault (Ig)

v

thresholds, priorities and time delays can be set for 10 other alarms. They may be

b

selected from a list of 91 alarms

Set the outputs of the SDx relays

This is required when the user wants to change the standard configuration and

assign different signals to the 2 outputs of the SDx relay.

RCU (Remote Control Utility)

The RCU utility can be used to test communication for all the devices connected

to the Modbus network. It is designed for use with Compact NSX, Compact,

Advantys OTB and Power Meter devices. It offers a number of functions.

Mini supervisor

Display of I, U, f, P, E and THD measurements for each device, via navigation.

b

Display of ON/OFF status.

b

Open and close commands for each device

A common or individual password must first be entered.

When all functions have been tested, this utility is replaced by the supervision

software selected for the installation.

Two utilities, RSU and RCU, are available to assist in

starting up a communicating installation.

They can be downloaded from the Schneider Electric

internet site and include a "Live update" function that

enables immediate updating.

DB118723

RCU: Remote Control Utility for communication tests.

PB104805

PB104806

RSU: Micrologic Remote Setting Utility.