Background Image
Table of Contents Table of Contents
Previous Page  52 / 148 Next Page
Information
Show Menu
Previous Page 52 / 148 Next Page
Page Background

A-36

Circuit breakers equipped with a control unit offering integrated

earth-leakage protection and an external rectangular sensor

Rated current (A)

630… 3200

Compact

NS630b to 1000 N/L

NS1600b to 3200

NS1250 and 1600 N

PB104844_ME

PB104845_SE

General circuit breaker characteristics

page A-12

Compact NS630b to 3200 circuit breakers are presented in the “Protection of

distribution systems” section.

Accompanying control units

page A-22

Micrologic 7.0 A electronic control units offer earth-leakage protection as standard.

Earth-leakage protection using a Vigirex relay

Earth-leakage relay

Separate toroids

Rectangular sensors

PB100435_16_SE

051352_32_SE

06133779A

Compact circuit breaker + Vigirex relay combination

Vigirex relays may be used to add external earth-leakage protection to Compact NS

circuit breakers. The circuit breakers must be equipped with an MN or MX voltage

release. Vigirex relays are very useful when special time-delay or tripping-threshold

values are required, or when there are major installation constraints (circuit breaker

already installed and connected, limited space available, etc.).

Vigirex-relay characteristics:

rectangular sensors up to 3200 A

b

400 Hz distribution systems.

b

Options:

trip alarm by a fail-safe contact

b

pre-alarm LED and contact, etc.

b

Compliance with standards:

IEC 60947-2, appendix M

b

IEC/EN 60755: general requirements for residual current operated protective

b

devices

IEC/EN 6100-4-2 to 4-6: immunity tests

b

CISPR11: radio-frequency radiated and conducted emission tests

b

UL1053 and CSA22.2 No. 144 for RH10, RH21 and RH99 relays at supply

b

voltages up to and including 220/240 V.

Functions and characteristics

Earth-leakage protection

Overview of solutions

Earth-leakage protection is obtained by:

b

installing a Micrologic 7.0 A control unit

(Compact NS630b to 3200)

b

using a Vigirex relay and separate sensors

(all Compact circuit breakers).