A-29
Overview of functions
PB104863
S: Micrologic without measurement.
A: Micrologic with ammeter
E: Micrologic “Energy”
P: Micrologic “Power”
Note:
see the description of the Micrologic control units for
further details on protection and alarms, measurements,
waveform capture, histories, logs and maintenance indicators.
Four functional levels
The Compact can be integrated into a Modbus communication environment.
There are four possible functional levels that can be combined.
Switch-
disconnectors
Circuit breaker
Status indications
ON/OFF (O/F)
b
S A E P
Spring charged CH
b
S A E P
Ready to close
b
S A E P
Fault-trip SDE
b
S A E P
Connected / disconnected / test position
CE/CD/CT (CCM only)
b
S A E P
S A E P
Controls
MX1 open
b
S A E P
XF close
b
S A E P
Measurements
Instantaneous measurement information
b
A E P
Averaged measurement information
b
E P
Maximeter / minimeter
b
A E P
Energy metering
b
E P
Demand for current and power
b
E P
Power quality
b
Operating assistance
Protection and alarm settings
P
Histories
E P
Time stamped event tables
P
Maintenance indicators
A E P
Communication Modbus bus
The Modbus RS 485 (RTU protocol) system is an open bus on which communicating
Modbus devices (Compact NS with Modbus COM, Power Meter PM700, PM800,
Sepam, Vigilohm, Compact NSX, etc.) are installed. All types of PLCs and
microcomputers may be connected to the bus.
Addresses
The Modbus communication parameters (address, baud rate, parity) are entered
using the keypad on the Micrologic A, E, P. For a switch-disconnector, it is necessary
to use the RSU (Remote Setting Utility) Micrologic utility.
Modbus addresses
@xx
Circuit breaker manager
(1 to 47)
@xx + 50
Chassis manager
(51 to 97)
@xx + 200
Measurement manager
(201 to 247)
@xx + 100
Protection manager
(101 to 147)
The manager addresses are automatically derived from the circuit breaker address
@xx entered via the Micrologic control unit (the default address is 47).
Number of devices
The maximum number of devices that may be connected to the Modbus bus
depends on the type of device (Compact with Modbus COM, PM700, PM800,
Sepam, Vigilohm, Compact NSX, etc.), the baud rate (19200 is recommended),
the volume of data exchanged and the desired response time. The RS 485 physical
layer offers up to 32 connection points on the bus (1 master, 31 slaves).
A fixed device requires only one connection point (communication module on the
device). A drawout device uses two connection points (communication modules on
the device and on the chassis).
The number must never exceed 31 fixed devices or 15 drawout devices.
Length of bus
The maximum recommended length for the Modbus bus is 1200 meters.
Bus power source
A 24 V DC power supply is required (less than 20 % ripple, insulation class II).




