Background Image
Table of Contents Table of Contents
Previous Page  40 / 148 Next Page
Information
Show Menu
Previous Page 40 / 148 Next Page
Page Background

A-24

PB100771-24

Battery module

The battery module maintains display operation and communication with the

supervisor if the power supply to the Micrologic control unit is interrupted.

It is installed in series between the Micrologic control unit and the AD module.

Characteristics

battery run-time: 4 hours (approximately)

b

mounted on vertical backplate or symmetrical rail.

b

Battery module.

PB100781-32_SE

M6C.

M6C programmable contacts

These contacts are optional equipment for the Micrologic P control units.

They are described with the indication contacts for the circuit breakers.

Micrologic

Type P

Characteristics

M6C

Minimum load

100 mA/24 V

Breaking capacity (A)

p.f.: 0.7

V AC 240

5

380

3

V DC 24

1.8

48

1.5

125

0.4

250

0.15

M6C: external 24 V DC power supply required (consumption 100 mA).

PB100775-32

Lead-seal cover.

Spare parts

Lead-seal covers

A lead-seal cover controls access to the adjustment dials.

When the cover is closed:

it is impossible to modify settings using the keypad unless the settings lockout pin

b

on the cover is removed

the test connector remains accessible

b

the test button for the earth-fault and earth-leakage protection function remains

b

accessible.

Characteristics

transparent cover for basic Micrologic and Micrologic A, E control units

b

non-transparent cover for Micrologic P control units.

b

Spare battery

A battery supplies power to the LEDs identifying the tripping causes. Battery service

life is approximately ten years.

A test button on the front of the control unit is used to check the battery condition.

The battery may be replaced on site when discharged.

Functions and characteristics

Protection of distribution

systems

Micrologic control units

for Compact NS630b to 3200