A-23

DB128050

External sensor (CT).

External sensors

External sensor for earth-fault and neutral protection

The sensors, used with the 3P circuit breakers, are installed on the neutral conductor for:

neutral protection (with Micrologic P)

b

residual type earth-fault protection (with Micrologic A, E and P).

b

The rating of the sensor (CT) must be compatible with the rating of the circuit breaker:

NS630b to 1600 A - 400/1600 CT

b

NS1600b to 3200 A - 1000/4000 CT.

b

Rectangular sensor for earth-leakage protection

The sensor is installed around the busbars (phases + neutral) to detect the zero-

phase sequence current required for the earth-leakage protection. Rectangular

sensors are available in two sizes.

Inside dimensions (mm)

280 x 115 up to 1600 A for Compact NS630b to 1600 A

b

470 x 160 up to 3200 A for Compact NS1600b to 3200 A.

b

External sensor for source ground return protection

The sensor is installed around the connection of the transformer neutral point to earth

and connects to the Micrologic 6.0 control unit via an MDGF module to provide the

source ground return (SGR) protection.

06133779A

External sensor for source ground return protection.

PB100773-32

Long-time rating plug

Four interchangeable plugs may be used to limit the long-time threshold setting

range for higher accuracy.

The time delay settings indicated on the plugs are for an overload of 6 Ir (for further

details, see the characteristics on

page A-13

and

page A-17

).

As standard, control units are equipped with the 0.4 to 1 plug.

Long-time rating plug.

Setting ranges

Standard

Ir = In x… 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1

Low-setting option Ir = In x… 0.4 0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.8

High-setting option Ir = In x… 0.80 0.82 0.85 0.88 0.90 0.92 0.95 0.98 1

Off plug

No long-time protection (Ir = In for Isd setting)

Important:

long-time rating plugs must always be removed before carrying out insulation or

dielectric withstand tests.

PB101026-32A

External 24 V DC power-supply module

The external power-supply module makes it possible to use the display even if the

circuit breaker is open or not supplied (for the exact conditions of use, see the

“electrical diagrams” part of this catalogue).

This module powers both the control unit (100 mA) and M6C programmable contacts

(100 mA).

If the COM communication option is used, the communication bus requires 24 V DC

power supply. With the Micrologic A/E control unit, this module makes it possible to

display currents of less than 20 % of In.

With the Micrologic P, it can be used to display fault currents after tripping.

Characteristics

power supply:

b

110/130, 200/240, 380/415 V AC (+10 % -15 %)

v

24/30, 48/60, 100/125 V DC (+20 % -20 %)

v

output voltage: 24 V DC ±5 %, 1 A.

b

ripple < 1 %

b

dielectric withstand : 3.5 kV rms between input/output, for 1 minutew

b

overvoltage category: as per IEC 60947-1 cat. 4.

b

External 24 V DC power power supply module.

Protection of distribution

systems

Micrologic control units

for Compact NS630b to 3200