A-12

Functions and characteristics

Micrologic control units

Micrologic E “energy”

1

long-time threshold and tripping delay

2

overload alarm (LED) at 1.125 Ir

3

short-time pick-up and tripping delay

4

instantaneous pick-up

5

earth-leakage or earth-fault pick-up and tripping delay

6

earth-leakage or earth-fault test button

7

long-time rating plug screw

8

test connector

9

lamp test, reset and battery test

10

indication of tripping cause

11

digital display

12

three-phase bargraph and ammeter

13

navigation button "quick View" (only with Micrologic E)

14

navigation button to view menu contents

15

navigation button to change menu

Micrologic E control units protect power circuits. They

also offer measurements, display, communication and

current maximeters. Version 6 provides earth-fault

protection.

(1)

Display on FDM121 only.

Note:

Micrologic E control units come with a transparent lead-

seal cover as standard.

"Energy meter" measurements

In addition to the ammeter measurements of Micrologic A

Micrologic E control units measure and display:

current demand

b

voltages: phase to phase, phase to neutral, average

b

(1)

and unbalanced

(1)

instantaneous power: P, Q, S

b

power factor: PF

b

power demand: P demand

b

energy: Ep, Eq

b

(1)

, Es

(1)

.

Accuracy of active energy Ep is 2 % (including the sensors). The range of

measurement is the same as current with Micrologic A, depending of an external

power supply module (24 V DC).

Communication option

In conjunction with the COM communication option, the control unit transmits the

following:

settings

b

all "ammeter" and "energy" measurements

b

enable connection to FDM121

b

tripping causes

b

maximeter / minimeter readings.

b

Protection

Protection thresholds and delays are set using the adjustment dials.

Overload protection

True rms long-time protection.

Thermal memory: thermal image before and after tripping.

Setting accuracy may be enhanced by limiting the setting range using a different long-

time rating plug. Overload protection can be cancelled using a specific LT

rating plug "Off".

Short-circuit protection

Short-time (rms) and instantaneous protection.

Selection of I

2

t type (ON or OFF) for short-time delay.

Earth-fault protection

Source ground return earth fault protection.

Selection of I

2

t type (ON or OFF) for delay.

Neutral protection

On three-pole circuit breakers, neutral protection is not possible.

On four-pole circuit breakers, neutral protection may be set using a three-position

switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral

protection at Ir (4P 4d).

Zone selective interlocking (ZSI)

A ZSI terminal block may be used to interconnect a number of control units to provide

total discrimination for short-time and earth-fault protection, without a delay before

tripping.

Overload alarm

A yellow alarm LED goes on when the current exceeds the long-time trip threshold.

Programmable contacts

The programmable contacts may be used to signal events

(Ir, Isd, Alarm Ir, Alarm Ig, Ig). They can be programmed using the keypad on the

Micrologic E control unit or remotely using the COM option (BCM ULP) and RSU

software.

Fault indications

LEDs indicate the type of fault:

overload (long-time protection Ir)

b

short-circuit (short-time Isd or instantaneous li protection)

b

earth fault (Ig)

b

internal fault (Ap).

b

Trip history

The trip history displays the list of the last 10 trips. For each trip, the following

indications are recorded and displayed:

the tripping cause: Ir, Isd, li, Ig or Auto-protection (Ap) trips

b

the date and time of the trip (requires communication option).

b

Battery power

The fault indication LEDs remain on until the test/reset button is pressed. Under

normal operating conditions, the battery supplying the LEDs has a service life of

approximately 10 years.

Test

Amini test kit or a portable test kit may be connected to the test connector on the front

to check circuit-breaker operation. For Micrologic 6.0 E control units, the operation of

earth-fault or earth-leakage protection can be checked by pressing the test button

located above the test connector.

DB128038

14

15