A-8

1

long-time threshold and tripping delay

2

overload alarm (LED)

3

short-time pick-up and tripping delay

4

instantaneous pick-up

5

fixing screw for long-time rating plug

6

test connector

Protection

Protection thresholds and delays are set using the adjustment dials.

Overload protection

True rms long-time protection.

Thermal memory: thermal image before and after tripping.

Setting accuracy may be enhanced by limiting the setting range using a different

long-time rating plug.

Overload protection can be cancelled using a specific LT rating plug "Off".

Short-circuit protection

Short-time (rms) and instantaneous protection.

Selection of I

2

t type (ON or OFF) for short-time delay.

Earth-fault protection

Residual or source ground return earth fault protection.

Selection of I

2

t type (ON or OFF) for delay.

Neutral protection

On three-pole circuit breakers, neutral protection is not possible.

On four-pole circuit breakers, neutral protection may be set using a three-position

switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2) or

neutral protection at Ir (4P 4d).

Indications

Overload indication by alarm LED on the front; the LED goes on when the current

exceeds the long-time trip threshold.

Test

Amini test kit or a portable test kit may be connected to the test connector on the

front to check circuit-breaker operation after installing the trip unit or accessories.

Micrologic 2.0, 5.0 and 6.0 control units protect power

circuits. Micrologic 5.0 and 6.0 offers time

discrimination for short-circuits as well.

Note.

Micrologic control units are equipped with a transparent lead-

seal cover as standard.

Micrologic control units

For Compact NS630b to 3200

DB128030

Functions and characteristics