Background Image
Table of Contents Table of Contents
Previous Page  26 / 148 Next Page
Information
Show Menu
Previous Page 26 / 148 Next Page
Page Background

A-10

Micrologic control units

Micrologic A "ammeter"

1

long-time threshold and tripping delay

2

overload alarm (LED) at 1.125 Ir

3

short-time pick-up and tripping delay

4

instantaneous pick-up

5

earth-leakage or earth-fault pick-up and tripping delay

6

earth-leakage or earth-fault test button

7

long-time rating plug screw

8

test connector

9

lamp test, reset and battery test

10

indication of tripping cause

11

digital display

12

three-phase bargraph and ammeter

13

navigation buttons

Micrologic A control units protect power circuits.

They also offer measurements, display, communication

and current maximeters. Version 6 provides earth-fault

protection, version 7 provides earth-leakage protection.

Note.

Micrologic A control units come with a transparent lead-seal

cover as standard.

"Ammeter" measurements

Micrologic A control units measure the true (rms) value of currents.

They provide continuous current measurements from 0.2 to 1.2 In and are accurate

to within 1.5 % (including the sensors).

A digital LCD screen continuously displays the most heavily loaded phase (Imax) or

displays the I

1

, I

2

, I

3

, I

N

, I

g

,I∆

n

, stored-current (maximeter) and setting values by

successively pressing the navigation button.

The optional external power supply makes it possible to display currents < 20 % In.

Below 0.1 In, measurements are not significant. Between 0.1and 0.2 In, accuracy

changes linearly from 4 % to 1.5 %.

Communication option

In conjunction with the COM communication option, the control unit transmits the

following:

settings

b

all “ammeter” measurements

b

tripping causes

b

maximeter readings.

b

Protection

Protection thresholds and delays are set using the adjustment dials.

Overload protection

True rms long-time protection.

Thermal memory: thermal image before and after tripping.

Setting accuracy may be enhanced by limiting the setting range using a different

long-time rating plug.

Overload protection can be cancelled using a specific LT rating plug "Off".

Short-circuit protection

Short-time (rms) and instantaneous protection.

Selection of I

2

t type (ON or OFF) for short-time delay.

Earth-fault protection

Residual or source ground return earth fault protection.

Selection of I

2

t type (ON or OFF) for delay.

Residual earth-leakage protection (Vigi).

Operation without an external power supply.

q

Protected against nuisance tripping.

k

DC-component withstand class A up to 10 A.

Neutral protection

On three-pole circuit breakers, neutral protection is not possible.

On four-pole circuit breakers, neutral protection may be set using a three-position

switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral

protection at Ir (4P 4d).

Zone selective interlocking (ZSI)

A ZSI terminal block may be used to interconnect a number of control units to provide

total discrimination for short-time and earth-fault protection, without a delay before

tripping.

Overload alarm

A yellow alarm LED goes on when the current exceeds the long-time trip threshold.

Fault indications

LEDs indicate the type of fault:

overload (long-time protection Ir)

b

short-circuit (short-time Isd or instantaneous li protection)

b

earth fault or earth leakage (Ig or I∆n)

b

internal fault (Ap).

b

Battery power

The fault indication LEDs remain on until the test/reset button is pressed. Under

normal operating conditions, the battery supplying the LEDs has a service life of

approximately 10 years.

Test

Amini test kit or a portable test kit may be connected to the test connector on the

front to check circuit-breaker operation. For Micrologic 6.0 A and 7.0 A control units,

the operation of earth-fault or earth-leakage protection can be checked by pressing

the test button located above the test connector.

DB128033

Functions and characteristics