A-16

Micrologic control units

Micrologic P "power"

Functions and characteristics

DB101133

DB101134

Measurements .........................................................

The Micrologic P control unit calculates in real time all the electrical values (V, A, W,

VAR, VA, Wh, VARh, VAh, Hz), power factors and

cos

ϕ

factors.

The Micrologic P control unit also calculates demand current and demand power

over an adjustable time period. Each measurement is associated with a minimeter

and a maximeter.

In the event of tripping on a fault, the interrupted current is stored. The optional

external power supply makes it possible to display the value with the circuit breaker

open or not supplied.

Instantaneous values

The value displayed on the screen is refreshed every second.

Minimum and maximum values of measurements are stored in memory (minimeters

and maximeters).

Default display.

Display of a maximum

current.

Currents

I

rms

A

1

2

3

N

A

E-fault

E-leakage

I

max rms

A

1

2

3

N

A

E-fault

E-leakage

DB101135

DB117042

Voltages

U

rms

V

12

23

31

V

rms

V

1N

2N

3N

U

average rms

V

(U12 + U23 + U31) / 3

U

unbalance

%

Power, energy

P

active

, Q

reactive

, S

apparent

W, Var, VA Totals

E

active

, E

reactive

, E

apparent

Wh, VARh, VAh Totals consumed - supplied

Totals consumed

Totals supplied

Power factor

PF

Total

Frequencies

F

Hz

Display of a voltage.

Display of a power.

Demand metering

The demand is calculated over a fixed or sliding time window that may be

programmed from 5 to 60 minutes. According to the contract signed with the power

supplier, an indicator associated with a load shedding function makes it possible to

avoid or minimise the costs of overrunning the subscribed power. Maximum demand

values are systematically stored and time stamped (maximeter).

DB101137

DB101138

Currents

I

demand

A

1

2

3

N

A

E-fault

E-leakage

I

max demand

A

1

2

3

N

A

E-fault

E-leakage

Power

P, Q, S

demand

W, Var, VA Totals

P, Q, S

max demand

W, Var, VA Totals

Display of a frequency.

Display of a demand power.

PB104850

Minimeters and maximeters

Only the current and power maximeters may be displayed on the screen.

Time-stamping

Time-stamping is activated as soon as time is set manually or by a supervisor.

No external power supply module is required (max. drift of 1 hour per year).

Reset

An individual reset, via the keypad or remotely, acts on alarms, minimum and

maximum data, peak values, the counters and the indicators.

Additional measurements accessible with the COM option

Some measured or calculated values are only accessible with the COM

communication option:

I

b

peak /

2

, (I

1

+ I

2

+ I

3

)/3, I

unbalance

load level in % Ir

b

total power factor.

b

The maximeters and minimeters are available only via the COM option for use with

a supervisor.

ION Enterprise Power Management software.