Kilowatt-hour meters (cont.)

Basic energy meters

Technical

Section 11

Dimensions

Section 12

7

DB118815

Circuit-breaker

Contactor

Circuit-breaker

Contactor

Load

Load

Kilowatt-hour meter

Kilowatt-hour meter

Example: meter on a load switching

Installation

b

b

The front panel of the product is IP40 and its housing is IP20.

b

b

Its installation must be appropriate to the operating conditions.

b

b

The protection must not be less than IP65 for outdoor use.

Use with a contactor

Ameasurement instrument is normally continually supplied.

For a non-continuous supply (load switching), we recommend that you place the

breaking device downstream from the measurement instrument to limit disturbances

on the module inputs.

These disturbances, particularly on inductive loads, may result in early ageing of the

device.

You must also place the measurement instrument at a distance from the breaking

device to limit the risk of disturbance.

Specific technical data

iEM2000, iEM2010, iEM2000T, iME1, iME1z and iME1zr specific technical data

iEM2000 iEM2010 iEM2000T

iME1

iME1z iME1zr

Direct measurement

Up to 40 A

Up to 63 A

Metering and activity indicator light

(yellow)

3,200 flashes per kWh

1,000 flashes per kWh

Wiring error indicator

Yes

Total meter (max. capacity) on one

phase

999 999.9 kWh

999.99 MWh

Total meter display

In kWh with 7 significant digits (not for iEM2000T)

In kWh or MWh with 5 significant digits. No decimal point in

kWh; 2 digits after the decimal point in MWh

Partial meter (max. capacity) on one

phase with RESET

-

-

99.99 MWh

Partial meter display

-

-

In kWh or MWh with 4 significant digits. No

decimal point in kWh; 2 digits after the decimal

point in MWh

Remote transfer

-

By static output:

- ELV insulation voltage: 4 kV, 50 Hz

- 20 mA/35 V DC max.

- 100 impulses of 120 ms per kWh

-

-

By NO impulse contact:

- ELV insulation voltage: 4 kV, 50 Hz

- 18 mA/24 V DC, 100 mA/230 V AC

- 1 impulse of 200 ms (contact

closing) per kWh

Connection

Single-phase circuit

DB118858

DB118858

to impulse meter

(iME1zr)

iEM2010

iME1 / iME1z / iME1zr.

Caution

b

b

Do not earth the CT secondary (S2).

b

b

You must comply with the routing direction of power cables in the current

transformer primary. Cables enter in "P1" and leave in "P2" to the loads.

DB114265

DB114264

1