Background Image
Table of Contents Table of Contents
Previous Page  220 / 408 Next Page
Information
Show Menu
Previous Page 220 / 408 Next Page
Page Background

7/88

Technical

Section 11

Dimensions

Section 12

Kilowatt-hour meters

Basic energy meters

7

Function

Digital kilowatt-hour meters designed for sub-metering of active energy (rms) consumed

by a single-phase or three-phase electric circuit with or without distributed neutral.

iEM2000T

40 A single-phase kilowatt-hour meter without display, with remote transfer of metering

impulses (static output).

iEM2000

40 A single-phase kilowatt-hour meter.

iEM2010

40 A single-phase kilowatt-hour meter with remote transfer of metering impulses

(static output).

iME1

Single-phase kilowatt-hour meter.

iME1z

Single-phase kilowatt-hour meter with partial meter.

iME1zr

Single-phase kilowatt-hour meter with partial meter and remote transfer of metering

impulses (relay output).

Catalogue numbers

Type

Rating

(A)

Voltage

(V AC)

Tolerance

(V AC)

Width in

mod. of  9 mm

Cat. no.

Single-phase circuit (1L + N)

iEM2000

40

230

±20

2

A9MEM2000

iEM2010

40

230

±20

2

A9MEM2010

iEM2000T

40

230

±20

2

A9MEM2000T

iME1

63

230

±20

4

A9M17065

iME1z

63

230

±20

4

A9M17066

iME1zr

63

230

±20

4

A9M17067

Main technical data

iEM2000T

iEM2000/iEM2010 iME

Accuracy class

1

1

1

Frequency

48/62 Hz

48/62 Hz

48/62 Hz

Consumption

<10VA

<10VA

2.5 VA

Operating temp

-10°C to +55°C -10°C to +55°C

-25°C to +55°C

Connection by

tunnel terminals

Top terminals: 4 mm

2

Top terminals: 4 mm

2

Top terminals: 6 mm

2

Bottom terminals:

10 mm

2

Bottom terminals:

10 mm

2

Bottom terminals:

16 mm

2

Compliance

with standard

IEC 61557-12 :

- PMD/DD/K55/1

IEC 61557-12 :

- PMD/DD/K55/1

IEC 61557-12 :

- PMD/DD/K55/1

IEC 62053-21

(accuracy)

IEC 62053-21

(accuracy)

IEC 62053-21 (accuracy)

Sealable screw

shield

Yes

Yes

Yes

MID Compliance

No

Yes

No

PB110836

iEM2000T

PB108400

PB108401

iEM2000

iEM2010

iME1_IMAGE.eps

iME1zr.

Description

iEM2000, iEM2010, iEM2000T

1 Remote transfer pulse output (iEM2000T, iEM2010).

2 Green power-on indicator light.

3 Yellow metering indicator light (flashing).

4 Display unit (iEM2000, iEM2010).

5 Seal.

6 Allow the comb busbar to pass.

iME1, iME1z, iME1zr

1 Pulse output for remote transfer (iME1zr).

2 Flashing meter indicator.

3 Total or partial meter display (iME1z, iME1zr).

4 Wiring error indicator.

5 Push-button: total or partial meter display, reset partial meter (ME1z, ME1zr).

6 Sealing connection.

DB115816

DB118760_i

iEM2010

iME1zr.