7/87
Technical
Section 11
Dimensions
Section 12
7
AMP/VLT/FRE digital meters
Metering and
measurement
Application
The meters facilitate the real time monitoring of current, voltage and frequency.
Technical data
Supply voltage:
230Vac
Operating frequency:
50 - 60Hz
Display by red LED:
3 digits
Accuracy at full scale:
0.5% ± 1 digital
Consumption:
0.3VA
Connection:
Tunnel terminals for 2.5mm
2
cables
EMC electromagnetic
IEC EN 50081-1 and IEC EN 50082-2
compatibility:
Safety:
IEC EN 61010-1
Specific technical data
AMP 10A
Minimum value measured:
4% of rating
Measurement input
1VA
consumption:
AMP Multirange
Ratings:
In direct reading: 5A
By CT (not supplied) configurable on the front face
of the ammeter: 10, 15, 20, 25, 40, 50, 60, 100, 150,
200, 250, 400, 500, 600, 800, 1000, 1500, 2000,
2500, 4000, 5000A
Minimum value measured:
4% of rating
Measurement input
0.55VA
consumption:
VLT
Direct measurement:
0 - 600Vac
Input impedance:
2 M
Ω
Minimum value measured:
4% of rating
FRE
Minimum value measured:
20Hz
Maximum value measured: 100Hz
Full scale display:
99.9Hz
Type
Scale
Connection
with CT
Width in
18mm
ways
Part
number
Amp with direct connection
0 - 10A
Direct
2
15202
AMP with multirating
0 - 5000A As per rating 2
15209
VLT
0 - 600V
As per rating 2
15201
FRE
20 - 100Hz As per rating 2
15208
1 2 3 4
L
N
NL
230V
1 2 3 4
L
N
0-800V
230V
1 2 3 4
L
N
20-600V
230V