7/84
Technical
Section 11
Dimensions
Section 12
7
IC100, 1C2000, IC2000P+,
IC100k, abd IC Astro (cont.)
Twilight switches
Accessories selection table
Wall-mounted cell
Switchboard
cell
Programming
kit for PC
Memory
key
Digital wall-
mounted cell
Digital
switchboard
cell
Function
Wall-mounted photoelectric cell
Switchboard
photoelectric cell
Consists of a
programming device,
a memory key, a CDROM
and a 2 m USB cable
Saving and
duplicating
programs
Digital wall-mounted
photoelectric cell
Digital wall-mounted
photoelectric cell
Mounting
b
b
Delivered with its
fixing device for IC100
and IC200P+
b
b
Replaced by
CCT15268 for spare
part use
b
b
Cell connection:
by double insulation
2-conductor cable, not
to be laid next to mains
cables or water ducts,
maximum length: 25 m
Delivered
with 1 m cable
and its fixing
device
b
b
Delivered with its
fixing device
b
b
Cell connection:
by double insulation
2-conductor cable,
not to be laid next to
mains cables or water
ducts, maximum
length: 100 m
–
–
b
b
Delivered with its fixing device.
b
b
Cell connection:
v
v
by double insulation 2-conductor cable:
- 0.5 - 2.5 mm
2
for
CCT15260
- 0.25 - 1.5 mm
2
for
CCT15261
v
v
Not to be laid next to mains cables
or water ducts, maximum length:
- 100 m (2 x 1.5 mm
2
)
- 50 m (2 x 0.75 mm
2
)
Catalogue no. –
CCT15268
15281
CCT15860
CCT15861 CCT15260
CCT15261
Technical spécifications
Degree of
protection
IP54
IP65
IP54
–
–
IP55
IP66
IK05
–
IK05
–
–
–
–
Operating
temperature
-40°C to +70°C
-40°C to +70°C -40°C to +70°C
–
–
-40°C to +70°C -40°C to +70°C
Horizontally
orientable
–
–
90°
–
–
90°
90°
P83237
P116858
P106856
P93580
P93581
P116858
P116859
Load table
Type of lighting
(230 V AC)
Max. power
(for higher power, relay with a contactor)
IC100
IC2000
IC2000P+
IC Astro
IC 100k
Incandescent and halogen lamps
2300 W
2300 W
2300 W
2300 W
2600 W
Non-corrected / serial-corrected / dual mounted
fluorescent tubes with conventional ballast
2300 VA
2300 VA
26 x 36 W,
20 x 58 W,
10 x 100 W
26 x 36 W,
20 x 58 W,
10 x 100 W
26 x 36 W,
20 x 58 W,
10 x 100 W
Parallel corrected fluorescent tubes with conventional
ballast
400 VA
400 VA
10 x 36 W,
6 x 58 W,
2 x 100 W
10 x 36 W,
6 x 58 W,
2 x 100 W
10 x 36 W, 6 x 58 W,
2 x 100 W
Fluorescent tubes with electronic ballast
–
–
9 x 36 W,
6 x 58 W
9 x 36 W,
6 x 58 W
650 VA max.
Dual-mounted fluorescent tubes with electronic ballast
300 VA
300 VA
5 x (2 x 36 W),
3 x (2 x 58 W)
5 x (2 x 36 W),
3 x (2 x 58 W)
–
Fluocompact lamps with electronic ballast
9 x 7W, 7 x 11W,
7 x 15W, 7 x 20W,
7 x 23W
9 x 7 W, 7 x 11 W,
7 x 15 W, 7 x 20 W,
7 x 23 W
9 x 7 W, 7 x 11 W,
7 x 15 W, 7 x 20 W
9 x 7W, 7 x 11W,
7 x 15W, 7 x 20W
22 x 7W, 18 x 11W,
16 x 15W, 16 x 20W,
14 x 23W
Fluocompact lamps with conventional ballast
1500 VA
1500 VA
–
–
–
Parallel-corrected mercury and sodium vapour lamps 400 VA
400 VA
250 VA
250 VA
800 VAmax. (80uF)
Non-corrected/ serial-corrected mercury and sodium
vapour lamps
1000 VA
1000 VA
–
–
–
Motor
–
–
–
–
2300 VAmax.