Acti 9 smartlink (cont.)

Control, remote control,

indication

Technical

Section 11

Dimensions

Section 12

6

Acti 9 Smartlink Modbus Slave technical characteristics

Characteristics of the Modbus link

Link

Modbus, RTU, RS485 serial connection

Transmission

Transfer rate

9600 baud ... 19200 baud, self-adaptable

Medium

Shielded cable, double twisted pair

Protocol

Master/Slave

Type of device

Slave

Modbus addressing range

1 to 99

Maximum length of the bus

1000 m

Type of bus connector

4-pin connector

Acti 9 Smartlink Ethernet technical characteristics

Characteristics of the Ethernet link

Link

10/100 MB Ethernet

Protocol

Modbus TCP server

http (Web pages)

Address mode

Static and dynamic (supplied, by default, in dynamic mode)

Characteristics of Gateway

Protocol

Modbus TCP/IP -> Modbus SL

Modbus slave number

8

Modbus addressing range

1 to 247

Characteristics of the Modbus Master link

Link

Modbus serial connection, RTU, RS485

Transmission

Transfer rate

9600 baud ... 19200 baud, self-adaptable

Support

Shielded cable, double twisted pair

Maximum length of the bus

1000 m

Type of bus connector

4-pin connector

Characteristics of the analog inputs

Number

2

Type

Separate configuration for each input, either 0-10 V or 4-20 mA

Measuring accuracy

1/100 full scale

Resolution

12 bits

Acquisition time

500 ms

Isolation

No isolation between channels

Power supply

0-24 V DC

Type of cable

Shielded cable, double twisted pair

Maximum cable length

30 m

Protection

Short-circuit protection

Weight (g)

Acti 9 Smartlink

Type

Acti 9 Smartlink Modbus Slave

195

Acti 9 Smartlink Ethernet

180

Dimensions (mm)

DB124330

359

42

22.5

Acti 9 Smartlink Modbus Slave

DB406390

359

42

22.5

Acti 9 Smartlink Ethernet