6/21
Acti 9 smartlink (cont.)
Control, remote control,
indication
Technical
Section 11
Dimensions
Section 12
6
Acti 9 Smartlink Modbus Slave technical characteristics
Characteristics of the Modbus link
Link
Modbus, RTU, RS485 serial connection
Transmission
Transfer rate
9600 baud ... 19200 baud, self-adaptable
Medium
Shielded cable, double twisted pair
Protocol
Master/Slave
Type of device
Slave
Modbus addressing range
1 to 99
Maximum length of the bus
1000 m
Type of bus connector
4-pin connector
Acti 9 Smartlink Ethernet technical characteristics
Characteristics of the Ethernet link
Link
10/100 MB Ethernet
Protocol
Modbus TCP server
http (Web pages)
Address mode
Static and dynamic (supplied, by default, in dynamic mode)
Characteristics of Gateway
Protocol
Modbus TCP/IP -> Modbus SL
Modbus slave number
8
Modbus addressing range
1 to 247
Characteristics of the Modbus Master link
Link
Modbus serial connection, RTU, RS485
Transmission
Transfer rate
9600 baud ... 19200 baud, self-adaptable
Support
Shielded cable, double twisted pair
Maximum length of the bus
1000 m
Type of bus connector
4-pin connector
Characteristics of the analog inputs
Number
2
Type
Separate configuration for each input, either 0-10 V or 4-20 mA
Measuring accuracy
1/100 full scale
Resolution
12 bits
Acquisition time
500 ms
Isolation
No isolation between channels
Power supply
0-24 V DC
Type of cable
Shielded cable, double twisted pair
Maximum cable length
30 m
Protection
Short-circuit protection
Weight (g)
Acti 9 Smartlink
Type
Acti 9 Smartlink Modbus Slave
195
Acti 9 Smartlink Ethernet
180
Dimensions (mm)
DB124330
359
42
22.5
Acti 9 Smartlink Modbus Slave
DB406390
359
42
22.5
Acti 9 Smartlink Ethernet