Background Image
Table of Contents Table of Contents
Previous Page  130 / 408 Next Page
Information
Show Menu
Previous Page 130 / 408 Next Page
Page Background

6/20

Technical

Section 11

Dimensions

Section 12

6

Acti 9 smartlink (cont.)

Control, remote control,

indication

Common technical characteristics

Power supply

Rated

24 V DC ± 20 %

Maximum input current

1.5 A

Maximum inrush current

3 A

Meter

Capacity

2

32

pulses per input

Input characteristics

Number of channels

Acti 9 Smartlink Modbus Slave

11 of 2-input channels

Acti 9 Smartlink Ethernet

7 of 2-input channels

Type of input

Current collector Type 1 IEC 61131-2

Maximum cable length

500 m

Rated voltage

24 V DC

Voltage limits

24 V DC ± 20 %

Rated current

2.5 mA

Maximum current

5 mA

Filtering time

In state 1

2 ms

In state 0

2 ms

Isolation

No isolation between channels

Negative sequence voltage protection

Yes

Output characteristics

Number of output channels

Acti 9 Smartlink Modbus Slave

11

Acti 9 Smartlink Ethernet

7

Type of output

24 V DC 0.1 A current source

Maximum cable length

500 m

Rated voltage

Voltage

24 V DC

Maximum current

100 mA

Filtering time

In state 1

2 ms

In state 0

2 ms

Voltage drop (voltage in state 1)

1 V max

Maximum inrush current

500 mA

Leakage current

0.1 mA

Overvoltage protection

33 V DC

Environmental characteristics

Temperature

Operating

-25°C ... +60°C (if vertical mounting, limited to 50°C)

Storage

-40°C…+80°C

Tropicalization

Treatment 2 (relative humidity of 93% at 40°C)

Resistance to voltage dips

10 ms, class 3 as per IEC 61000-4-29

Degree of protection

IP20

Pollution degree

3

Altitude

Operating

0 … 2000 m

Vibration resistance

As per IEC 60068.2.6

1 g / ± 3.5 mm - 5 Hz to 300 Hz - 10 cycles

Shock resistance

As per IEC 60068.2.2 7

15 g / 11 ms

Immunity to electrostatic discharge

As per IEC 61000-4-2

Air: 8 kV

Contact: 4 kV

Immunity to radiated magnetic fields

As per IEC 61000-4-3

10 V/m - 80 MHz to 3 GHz

Immunity to fast transients

As per IEC 61000-4-4

1 kV for inputs/outputs and Modbus communication.

2 kV for 24 DC power supply - 5 kHz - 100 kHz

Immunity to conducted magnetic fields

As per IEC 61000-4-6

10 V from 150 kHz to 80 MHz

Immunity to magnetic fields at mains frequency

As per IEC 61000-4-8

30 A/m

Resistance to corrosive atmospheres

As per IEC 60721-3-3

Level 3C2 on H

2

S / SO

2

/ NO

2

/ Cl

2

Fire resistance

For live parts

At 960°C 30 s / 30 s as per IEC 60 695-2-10 and IEC 60 695-2-11

For other parts

At 650°C 30 s / 30 s as per IEC 60 695-2-10 and IEC 60 695-2-11

Salt spray test

As per IEC 60068.2.52

Severity 2

Environment

In compliance with the RoHS directive

Additional characteristics

Duration of saving memory

10 years

Prefabricated cables characteristics

Dielectric resistance

1 kV / 5 min

Minimum draw-out resistance

20 N