6/19
Technical
Section 11
Dimensions
Section 12
6
Acti 9 smartlink (cont.)
Control, remote control,
indication
Acti 9 Smartlink Modbus Slave
Thumbwheels
b
b
Definition of the address
in the Modbus network
Signalisation
b
b
Indication of operation of the
communication system and the state
of Acti 9 Smartlink Modbus Slave
Serial port connector
RS485 Modbus (Slave)
b
b
Pin 1: D1 Modbus
b
b
Pin 2: D0 Modbus
b
b
Pin 3: shielding
b
b
Pin 4: common/0 V
24 V DC power supply
connector
Protected against voltage
reversals
b
b
Pin 1: 0 V
b
b
Pin 2:+24 V DC
Ti24 connector
11 input/output channels
Protected at input against voltage
reversals
Protected at output by current limiting
b
b
Pin 1: 0 V
b
b
Pin 2: I1 Input 1
b
b
Pin 3: I2 Input 2
b
b
Pin 4: Q Output
b
b
Pin 5: +24 V DC
Signalisation
b
b
Indication of operation of the
communication system and the state
of Acti 9 Smartlink Ethernet
24 V DC power supply
connector
Protected against voltage
reversals
b
b
Pin 1: 0 V
b
b
Pin 2:+24 V DC
Analog connector
2 configurable input points, either
0-10 V or 4-20 mA
b
b
Pin 1: 0 V
b
b
Pin 2: AI1 Input 1
b
b
Pin 3: AI2 Input 2
b
b
Pin 4: +24 V DC
Ethernet connector
100 base T - RJ45
Serial port connector
Modbus RS485 (Master)
b
b
Pin 1: D1 Modbus
b
b
Pin 2: D0 Modbus
b
b
Pin 3: shielding
b
b
Pin 4: common/0V
Ti24 connector
7 input/output channels
Protected at input against voltage
reversals
Protected at output by current limiting
b
b
Pin 1: 0 V
b
b
Pin 2: I1 Input 1
b
b
Pin 3: I2 Input 2
b
b
Pin 4: Q Output
b
b
Pin 5: +24 V DC
Acti 9 Smartlink Ethernet
PB107753-175
PB113286-175