Thermal management system

Help table to calculate corrected surfaces

Spacial floor-standing enclosures

Installation mode

H (mm) W (mm) D (mm) 1

2

3

4

5

6

7

1200 800

300

2.71 2.33 2.57 2.18 2.42 2.04 1.87

1000 300

3.23 2.75 3.08 2.60 2.94 2.46 2.25

1200 400

4.13 3.55 3.94 3.36 3.74 3.17 2.83

1400 600

300

2.52 2.18 2.35 2.02 2.18 1.85 1.72

400

2.86 2.52 2.63 2.30 2.41 2.07 1.90

800

300

3.11 2.66 2.94 2.49 2.77 2.32 2.16

400

3.47 3.02 3.25 2.80 3.02 2.58 2.35

1000 400

4.09 3.53 3.86 3.30 3.64 3.08 2.80

1200 400

4.70 4.03 4.48 3.81 4.26 3.58 3.25

1600 600

300

2.84 2.46 2.65 2.27 2.46 2.08 1.95

400

3.22 2.83 2.96 2.58 2.70 2.32 2.15

800

300

3.50 2.99 3.31 2.80 3.12 2.61 2.44

400

3.90 3.39 3.65 3.14 3.39 2.88 2.66

1000 300

4.16 3.52 3.97 3.33 3.78 3.14 2.93

400

4.59 3.95 4.34 3.70 4.08 3.44 3.16

1200 300

4.82 4.06 4.63 3.86 4.44 3.67 3.42

400

5.28 4.51 5.02 4.26 4.77 4.00 3.66

1800 600

300

3.17 2.74 2.95 2.52 2.74 2.30 2.18

400

3.58 3.14 3.29 2.86 3.00 2.57 2.40

500

3.98 3.55 3.62 3.19 3.26 2.83 2.62

800

300

3.90 3.32 3.68 3.11 3.47 2.89 2.72

400

4.34 3.76 4.05 3.47 3.76 3.18 2.96

500

4.77 4.20 4.41 3.84 4.05 3.48 3.20

600

5.21 4.63 4.78 4.20 4.34 3.77 3.43

1000 400

5.10 4.38 4.81 4.09 4.52 3.80 3.52

500

5.56 4.84 5.20 4.48 4.84 4.12 3.77

1200 400

5.86 4.99 5.57 4.70 5.28 4.42 4.08

500

6.35 5.48 5.99 5.12 5.63 4.76 4.34

1600 400

7.38 6.22 7.09 5.94 6.80 5.65 5.20

500

7.92 6.77 7.56 6.41 7.20 6.05 5.49

2000 600

300

3.49 3.01 3.25 2.77 3.01 2.53 2.41

400

3.94 3.46 3.62 3.14 3.30 2.82 2.65

500

4.38 3.90 3.98 3.50 3.58 3.10 2.89

800

300

4.30 3.66 4.06 3.42 3.82 3.18 3.01

400

4.77 4.13 4.45 3.81 4.13 3.49 3.26

500

5.24 4.60 4.84 4.20 4.44 3.80 3.52

600

5.71 5.07 5.23 4.59 4.75 4.11 3.78

1000 400

5.60 4.80 5.28 4.48 4.96 4.16 3.88

500

6.10 5.30 5.70 4.90 5.30 4.50 4.15

1200 400

6.43 5.47 6.11 5.15 5.79 4.83 4.50

500

6.96 6.00 6.56 5.60 6.16 5.20 4.78

600

7.49 6.53 7.01 6.05 6.53 5.57 5.06

1600 400

8.10 6.82 7.78 6.50 7.46 6.18 5.73

500

8.68 7.40 8.28 7.00 7.88 6.60 6.04

600

9.26 7.98 8.78 7.50 8.30 7.02 6.35

Installation mode

1

Accessible from every side

2

Placed against a wall

3

On the end when suited

4

On the end when suited, placed against a wall

5

In the middle when suited

6

In the middle when suited, placed against a wall

7

In the middle when suited, placed against a wall with

the top covered

The surfaces are given in m

2

.

Use ProClima