316

DD385393

Spacial SFP

Prisma functional system

Characteristics

Presentation

Decisions concerning the Form of separation

and the degree of protection are the subject

of an agreement between the manufacturer

and the user.

In most installations, Spacial SFP cubicles do not

require partitioning. In this case, the switchboard

is a Form 1.

Safety being one of its foremost goals,

Schneider Electric offers options and features

that go well beyond the recommendations

of the standard.

The protection of life and property is a standard

feature due to:

>

front plates that require a tool to be removed

>

keylocks on doors, some of which provide

access to live parts

>

the systematic installation of terminal shields

on Compact NSX circuit breakers and

Compact INS and INV switch-disconnectors.

What is more, Spacial SFP offers different levels

of partitioning to create separations inside the

cubicles and thus create Form 2b, 3b, 4a & 4b

electrical switchboards.

Electrical switchboards must meet the degree

of protection IP2X to comply with standard

IEC 61439-1 and 2.

The protection of life and property is ensured by the systematic installation of terminal shields

on Compact NSX circuit breakers and on Compact INS and INV switch-disconnectors

(see the pages on the functional units).