![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0316.jpg)
316
DD385393
Spacial SFP
Prisma functional system
Characteristics
Presentation
Decisions concerning the Form of separation
and the degree of protection are the subject
of an agreement between the manufacturer
and the user.
In most installations, Spacial SFP cubicles do not
require partitioning. In this case, the switchboard
is a Form 1.
Safety being one of its foremost goals,
Schneider Electric offers options and features
that go well beyond the recommendations
of the standard.
The protection of life and property is a standard
feature due to:
>
front plates that require a tool to be removed
>
keylocks on doors, some of which provide
access to live parts
>
the systematic installation of terminal shields
on Compact NSX circuit breakers and
Compact INS and INV switch-disconnectors.
What is more, Spacial SFP offers different levels
of partitioning to create separations inside the
cubicles and thus create Form 2b, 3b, 4a & 4b
electrical switchboards.
Electrical switchboards must meet the degree
of protection IP2X to comply with standard
IEC 61439-1 and 2.
The protection of life and property is ensured by the systematic installation of terminal shields
on Compact NSX circuit breakers and on Compact INS and INV switch-disconnectors
(see the pages on the functional units).
Form 1 partitioning