126

®

Safety is a major concern for everyone, but can only be achieved

with knowledge of how electrical equipment behaves in the event

of a fire. Cablofil steel wire cable tray has been successfully

tested and proven to meet all fire safety requirements.

1

Standard DIN 4102-12

The German DIN standard serves as a reference. As there is

no European standard on fire resistance specifically for cable

trays. The German standard specifies that the entire system of

cable trays, accessories and cables must be tested in an oven

which is at least 3 m long for a period of 30, 60 or 90 minutes at

temperatures of up to 1000°C.

The test aims to verify whether the electrical system is working

properly and make sure that sources of critical data (emergency

lighting, ventilators, emergency exit, fire alarm, etc.) can resist

long enough to provide assistance in the event of a fire.

2

Recognised independent laboratories

The IBMB (Institut für Baustoffe, Massivbau & Brandschutz) and

FIRES laboratories are recognised centres for testing and issuing

the associated certificates. They ensure that the test conditions

described in the standard DIN 4102-12 are observed.

3

Test configuration

Cablofil steel wire cable tray standard products passed the tests

without the need to develop an extensive or specific range. The

configurations used by Legrand involve wire cable trays with two

different spans (1250 mm and 1500 mm) subject to a maximum

permissible load of between 2 kg/m and 20 kg/m. The increase in

temperature follows the temperature curve (ETK) defined by DIN

4102-12.

The E 90 test does not in itself validate a wire cable tray, but

validates the combination of Cablofil steel wire cable tray with a

specific type of cable. This underlines the complexity, as well as

the relevance, of these tests, which have already been passed by a

number of cable types. Cables are tested in pairs.

The surprising

appearance of the

cable tray after the test

is quite normal. The

mechanical properties

of the cables and cable

tray are impaired but

they achieved their

objective; to ensure

the durability of the

installation for a given

period.

Fire resistance

IN THIS SECTION...

Fire resistance

1. Standard DIN 4102-12

2. Recognised independent

laboratories

3. Test configuration

4. Samples of configurations

tested

Fire resistance

and protection

Before test

During test

After test

Period

Certification

> 30 minutes

E 30

> 60 minutes

E 60

> 90 minutes

E 90