Cat. Nos.

0046 70 0046 81 0046 72 0046 77 0046 78 0046 79 0046 73 0046 80 0046 82 0046 83 0046 74 0046 84 0046 85 0046 86

Number of modules

1

2

2

2

2

2

4

4

4

4

4

4

4

4

Connection

Direct

Via a current transformer

Single phase

Three phase

Max. current

32 A 36 A 63 A 63 A 63 A 63 A 63 A 63 A 63 A 63 A 5 A

(CT)

5 A

(CT)

5 A

(CT)

5 A

(CT)

Metering and

measurement

Total active energy

Total reactive energy

Partial active energy (reset)

Partial reactive energy (reset)

Active power

Reactive power

Apparent power

Current

Voltage

Frequency

Power factor

Time-of-use

Average active power

Max. average active power value

Dual tariff

Communication Pulse output

RS 485 interface

MID compliant

Operating

conditions

Reference temperature

23 °C ± 2 °C

Operating temperature

-20 to +55 °C

-10 to +45 °C

-5 to +55 °C

Storage temperature

-40 to +70 °C

-25 to +70 °C

-25 to +70 °C

Consumption

8 VA

4 VA per phase

1 VA per phase

Heat dissipation

6 . 5 W

6 W

4 W

n

Technical information

Single phase meters Cat. Nos. 0046 70/72/77/78/79/81

LCD display : 7 digits

Resolution : 0 . 1 kWh

Maximum indication : 99999 . 9 kWh

Metrological LED : 1 Wh/pulse (Cat. No. 0046 70 : 0 . 5 Wh/pulse)

Accuracy (EN 62053-21) : class 1

Reference voltage Un : 230 V-240 V

Reference frequency : 50-60 Hz

Three phase meters Cat. Nos. 0046 73/74/80/82/83/84/85/86

LCD display :

8 digits

Resolution : 0 . 01 kWh

1

Maximum indication : 99999 . 99 kWh

1

Metrological LED : 0 . 1 Wh/pulse or 1 Wh/pulse

Active energy accuracy (EN 62053-21) : class 1

Reactive energy accuracy (EN 62053-23) : class 2

Reference voltage Un :

- Single phase : 230-240 V

- Three phase : 230(400)-240(415) V

Operating limit range (EN 62053-21, EN 62053-23) :

- Single phase : 110 to 254 V

- Three phase : 110(190) to 254(440) V

1 : For direct connection meters

If connected via transformers, the resolution and maximum indication depend on the transformation ratios of these transformers

n

Interfacing with IP communication network

Pulse electricity meters

RS 485 - Fieldbus

IP network - Communication bus

Concentrator

Cat. No. 0046 87

Connects up to 7 pulse

electricity meters

RS 485/IP converter

Cat. No. 0046 89

RS 485 electricity meters

EMDX

3

electrical energy meters

4

rail mounting