Table of Contents Table of Contents
Previous Page  70 / 210 Next Page
Information
Show Menu
Previous Page 70 / 210 Next Page
Page Background

70

Pack

Cat. Nos.

Single phase current transformers (CT)

Used with ammeters, electricity meters or

multi-function measuring units

Provide a 0 to 5 A current at the secondary,

proportional to the primary current

For fixing on plates, EN 60715

4

rail

Cat. Nos. 0046 31/34/36, or bars

Secondary connected by terminals or lugs

Precision class 1%

For 16 x 12 . 5 mm bar and Ø21 mm cable

Transformation ratio

Output (VA)

1

0046 31

50/5

1. 25

1

0046 34

100/5

2 . 5

1

0046 36

200/5

5 . 5

For 20 . 5 x 12 . 5 and 30 x 10 . 5 mm bar and

Ø23 mm cable

1

0047 75

300/5

11

For 40 . 5 x 10 . 5 mm bar and Ø35 mm cable

1

0046 38

400/5

12

For 65 x 32 mm bar

1

0047 76

600/5

12

1

0047 77

800/5

15

1

0047 78

1000/5

20

For 84 x 34 mm bar

1

0047 79

1250/5

15

For 127 x 38 mm bar

1

0046 45

1500/5

15

1

0046 46

2000/5

20

For 127 x 54 mm bar

1

0047 80

2500/5

50

1

0046 48

4000/5

50

Three phase current transformers (CT)

Used with ammeters, electricity meters or

multi-function measuring units

Provide a 0 to 5 A current at the secondary,

proportional to the primary current

For fixing directly on bars

Secondary connected by terminals or lugs

Precision class 1%

For three 20 . 5 x 5 . 5 mm bars

Transformation ratio

Output (VA)

1

0046 98

250/5

3

For three 30 . 5 x 5 . 5 mm bars

1

0046 99

400/5

4

0047 79

n

Current transformers (CT)

Technical information

Degree of protection : IP 20

Operating frequency : 50/60 Hz

Dimensions

• Single phase CTs

Cat. Nos. 0046 31/34/36 for 16 x 12 . 5 mm bar and Ø21 mm cable

Fixing on EN 60715 rail

65

44

47,5

30

Cat. Nos. 0047 76/77/78 for 65 x 32 mm bar

Cat. No. 0047 79 for 84 x 34 mm bar

Fixing on bar

Cat. Nos. 0046 45/46 for 127 x 38 mm bar

Cat. Nos. 0047 80 and 0046 48 for 127 x 54 mm bar

Fixing on bar

• Three phase CT

Cat. No. 0046 98 for three 20 . 5 x 5 . 5 mm bars

Cat. No. 0046 99 for three 30 . 5 x 5 . 5 mm bars

Fixing on bar

Determination of the max. distance between CT and meter

Cat. Nos.

A B C D Ø Fixing centres

on plate

0047 75

56 42 94 50 23

50 x 45

0046 38

77 46 107 54 35

54 x 45

Cat. Nos.

A B C D

0047 76/77/78

90 90 94 40

0047 79

96 87 116 58

Cat. Nos.

A B

0046 45/46

99 58

0046 48/0 047 80

125 40

Cat. Nos.

A B C

0046 98

107 58 . 5 25

0046 99

135 66 . 5 30

Cat. Nos.

Max. power

of CT

Meter

consump.

(W)

Max. loss in

capac. (VA)

Max. distance bet. CT & meter (m)

Wiring

2 . 5 mm

2

Wiring

4 mm

2

Wiring

6 mm

2

0046 31

1 . 25

0 . 5

0 . 75

1 . 8

2 . 7

3 . 9

0046 34

2 . 5

0 . 5

2

4 . 9

7 . 1

10 . 4

0046 98

3

0 . 5

2 . 5

6 . 1

8 . 9

13

0046 99

4

0 . 5

3 . 5

8 . 5

12 . 4

18 . 1

0046 36

5 . 5

0 . 5

5

12 . 2

17 . 8

25 . 9

0047 75

11

0 . 5

10 . 5

25 . 5

37 . 3

54 . 4

0046 38

0047 76

12

0 . 5

11 . 5

28

40 . 8

59 . 6

0047 77/79

0046 45

15

0 . 5

14 . 5

35 . 3

51 . 5

75 . 2

0046 46

0047 78

20

0 . 5

19 . 5

47 . 4

69 . 3

101 . 1

0047 80

0046 48

50

0 . 5

49 . 5

120 . 4

175 . 8

256 . 7

C

D

B

45

A

A

C

B

D

160

B

87

A

C

9

B

37

A

56

Cat. No. 0047 75 for 20 . 5 x 12 . 5 and 30 x 10 . 5 mm bar and Ø23 mm cable

Cat. No. 0046 38 for 40 . 5 x 10 . 5 mm bar and Ø35 mm cable

Fixing on EN 60715 rail or on plate

current transformers CT